Page 25
Integrated Control
RED LED 
Flash Code
Diagnostic Codes / Status of Furnace
Off No power to control or board fault detected
On Board fault detected,
Heartbeat
1
Control powered - displayed during all modes of operation if no errors are detected
1 Reverse Line Voltage Polarity
2 Improper Earth Ground
3 Burner failed to light, or lost ame during heat demand
4 Low Flame Signal - check ame sensor
5 Watchguard - burner failed to light, exceeded maximum number of retries or 
recycles.
6 Not Used
7 Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer 
than 3 minutes
8 Rollout Switch Open
9 Pressure Switch failed to close or opened during heat demand
10 Watchguard - Pressure Switch opened 5 times during one heat demand
11 Pressure Switch stuck closed prior to activation of combustion air inducer
12 Flame Sensed without gas valve energized
13 Low Line Voltage
Note - 1 Notes
Note A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
Note Last 10 error codes are stored in memory including when power is shut off to the 
unit. - To recall, pressand release button, most recent will be displayed rst, LED 
off for 3 sec, then next error code is displayed, etc. To clear error codes, depress 
and hold button longer than 5 seconds.
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
BLOWER OFF DELAY
RED LED
RECALL BUTTON
Figure 30 
TABLE 7
1/4” QUICK CONNECT TERMINALS
120HUM Humidier 120VAC
LINE 120VAC
XFMR Transformer 120VAC
CIRC Indoor blower 120VAC
EAC Indoor air qualityaccessory 
120VAC
NEUTRAL Common 120VAC
HUM24 Humidier 24VAC
3/16” QUICK CONNECT TERMINALS
COOL Cooling tap 24VAC
HEAT Heating tap 24VAC
FAN Continuous blower 24 VAC
PARK (no power) Park terminal for speed taps
FLAME / FS Flame Sense
24 COM Common 24VAC