Page 28
TABLE 10 
Manifold Pressure Settings at all Altitudes
Model 
Input Size
Gas 0 - 2000 ft. 2001 -4500 ft . 4501 - 7500 ft.
7501 - 10,000 
ft
Line Pressure in. wg.
Min Max
045
Nat 3.5 3.2 3.0 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 10.0 11.0 13.0
070
Nat 3.5 3.2 2.8 3.5 4.5 13.0
LP/Propane 10.0 10.0 10.0 10.0 11.0 13.0
090
Nat 3.5 3.2 2.7 3.5 4.5 13.0
LP/Propane 10.0 10.0 9.6 10.0 11.0 13.0
110
Nat 3.5 3.5 3.0 3.5 4.5 13.0
LP/Propane 10.0 10.0 9.6 10.0 11.0 13.0
135
Nat 3.5 3.5 2.9 3.5 4.5 13.0
LP/Propane 10.0 10.0 9.6 10.0 11.0 13.0
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment 
vestibule panel. The secondary limits (if equipped) are lo-
cated in the blower compartment, attached to the back 
side of the blower. These auto reset limits are factory-set 
and require no adjustment.
Flame Rollout Switches
These manually reset switches are located on the front of 
the box.
Pressure Switch
The pressure switch is located in the heating compartment 
adjacent to the combustion air inducer. The switch checks 
for proper combustion air inducer operation before allow-
ing ignition trial. The switch is factory-set and requires no 
adjustment.
TABLE 11 
Pressure Switch and Gas Conversion Kits at all Altitudes
Model Input 
Size
High Altitude Pressure Switch Kit
High Altitude 
Natuarl Gas 
Orice Kit
LP/Propane Oricice Kit
Natuarl Gas 
Orice Kit
045 0-4500 ft 4501-7500 ft 7501-10,000 ft 7501-10,000 ft 0-7500 ft 7501-10,000 ft 0-7500 ft
070
No Change
80W52 80W51
73W37 11K49 73W81 73W81
110 80W52 80W51
090 80W52 80W51
110 80W57 80W52
135 80W52 80W51
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit instal-
lation instruction for the conversion procedure.
Temperature Rise
After the furnace has been started, and supply and return 
air temperatures have been allowed to stabilize, check the 
temperature rise
If necessary, adjust the blower speed to maintain the tem-
perature rise within the range shown on the unit nameplate. 
Increase the blower speed to decrease the temperature. 
Decrease the blower speed to increase the temperature 
rise. Failure to adjust the temperature rise may cause er-
ratic limit operation.
Fan Control
The heat fan-on time of 30 seconds is not adjustable. The 
heat fan-off delay (amount of time that the blower oper-
ates  after  the  heat  demand  has  been  satised)  may  be 
adjusted by changing the jumper position across the ve 
pins on the integrated control. The unit is shipped with a 
factory fan-off delay setting of 90 seconds. The fan-off de-
lay affects comfort and is adjustable to satisfy individual 
applications. Adjust the fan-off delay to achieve a supply 
air temperature between 90° and 110°F at the moment 
that the blower is de-energized. Longer off delay settings 
provide lower return air temperatures; shorter settings 
provide higher return air temperatures. See gure 32