Page 10
NOTE - During abnormal conditions such as low supply 
voltage or low outdoor temperatures and the low re pres-
sure switch does not close, the combustion air inducer will 
switch to high re. After a 15 second pre-purge the high 
re pressure switch will close and the unit will begin op-
eration  on  high  re.  After  10  to  20  seconds  of  high  re 
operation the unit will switch to low re.
After  the  15-second  pre-purge  period,  the  SureLight  ig-
nitor warms up for 20 seconds after which the gas valve 
opens for a 4-second trial for ignition. The ignitor remains 
energized during the trial until ame is sensed. If ignition 
is not proved during the 4-second period, the control will 
try four more times with an inter purge and warm-up time 
between trials of 35 seconds. After a total of ve trials for 
ignition  (including  the  initial  trial),  the  control  goes  into 
Watchguard- Flame Failure mode. After a 60-minute reset 
period, thecontrol will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP 
Switch
The control can be utilized in two modes: SINGLE-STAGE 
thermostat  or  TWO-STAGE  thermostat.  The  thermostat 
selection is made using a  DIP switch and must be  posi-
tioned for the particular application. DIP switch 1, labeled 
T”STAT HEAT STAGE  is  factory-set  in  the OFF  position 
for use with a two-stage thermostat. Move the DIP switch 
to ON for use with a single stage thermostat. While in the 
single-stage thermostat mode, the burners will always re 
on rst-stage heat. The combustion air inducer will oper-
ate on  low  speed and  indoor blower will  operate on low 
heat speed. The unit will switch to second stage heat af-
ter a “recognition period”. DIP switch 2, labeled SECOND 
STAGE DELAY, is factory set in the OFF position for a 7 
minute recognition period. The switch can be moved to the 
ON position for a 12 minute recognition period, after which 
time the unit will switch to secondstage heat. While in the 
two-stage thermostat mode, the burners will re on rst-
stage heat. The combustion air inducer will operate on low 
speed and indoor blower will operate on low heat speed. 
The unit will switch to second-stage heat on call from the 
indoor thermostat. If there is a simultaneous call for rst 
and second stage heat, the unit will re an rst stage heat 
and switch to second stage heat after 30 seconds of oper-
ation. See Sequence of Operation ow charts in the back 
of this manual for more detail.
TABLE 1 
SureLight
® 
Control 5 Pin Terminal Designation
Pin # Function
1 Ignitor
2 Combustion Air Inducer High 
Speed
3 Combustion Air Inducer Low 
Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 2 
SureLight
®
 Control 12 Pin Terminal Designation
Pin # Function
1 Gas Valve Second Stage
2 Second Stage Prove Switch
3 Rollout Switch In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve First Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 First Stage Prove Switch
TABLE 3 
SureLight
® 
Control 6 Pin Terminal Designation
Pin # Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6 Not Used