Page 9
I-UNIT COMPONENTS
EL297DFV(X) unit components are shown in FIGURE 1. 
The gas valve, combustion air inducer and burners can be 
accessed by removing the access panel. Electrical com-
ponents are  in the  control  box  (FIGURE  2)  found  in  the 
blower section.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
 CAUTION
Electrostatic  discharge  can  aect 
electronic components. Take precautions 
to neutralize electrostatic charge by 
touching your hand and tools to metal 
prior to handling the control.
A- Control Box
1. Control Transformer (T1)
A  transformer  located in  the control  box provides  power 
to the low voltage section of the unit. Transformers on all 
models  are  rated  40VA  with  a  120V  primary  and  a  24V 
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in se-
ries with line voltage. When the inner blower access panel 
is removed the unit will shut down.
Transformer
SureLight
®
 
Integrated Control
Interlock Switch
Circuit Breaker
FIGURE 2 
3. Circuit Breaker (CB8)
A  24V  circuit  breaker  is  also  located  in  the  control  box. 
The  switch  provides  overcurrent  protection  to  the  trans-
former (T1). The breaker is rated 3A at 32V. If the current 
exceeds this limit the breaker will trip and all unit opera-
tion will shutdown. The breaker can be manually reset by 
pressing the button on the face. See FIGURE 3.
PRESS TO RESET
FIGURE 3 
 WARNING
Shock hazard.
Disconnect power before servicing. Integrated 
control is not eld repairable. If control is inoperable, 
simply replace entire control.
Can cause injury or death. Unsafe operation will 
result if repair is attempted.
4. Integrated Control (A92)
Units are equipped with a communicating enabled Sure-
Light 
®
 two-stage, variable speed integrated control. This 
control is used with a communicating thermostat as part 
of a communicating comfort system. The control can also 
operate with a non-communicating conventional single or 
two-stage thermostat. The system consists of a ignition / 
blower control (FIGURE 4 and FIGURE 6) with control pin 
designations in TABLE 1, TABLE 2, TABLE 3 and ignitor 
(FIGURE 14). The control and ignitor work in combination 
to ensure furnace ignition and ignitor durability. The con-
trol provides gas ignition, safety checks and indoor blower 
control with two-stage gas heating. The furnace combus-
tion air inducer, gas valve and indoor blower are controlled 
in response to various system inputs such as thermostat 
signal, pressure and limit switch signal and ame signal. 
The control features a seven-segment LED display, indi-
cating furnace status (including indoor blower) and error 
codes. The LED ashes in single digits. The control also 
has two unpowered (dry) 1/4” contacts for a humidier and 
a 120 volt accessory terminal. Both rated at (1) one amp 
each.
Electronic Ignition
At the beginning of  the  heat cycle the integrated control 
monitors the rst stage and second stage combustion air 
inducer prove switch. The control will not begin the heating 
cycle if the rst stage prove switch is closed (by-passed). 
Likewise the integrated control will not begin the second 
stage  heating  cycle  if  the  second  stage  prove  switch  is 
closed, and will remain in rst stage heat. However, if the 
second  stage  prove  switch  closes  during  the  rst  stage 
heat pre-purge, the control will allow second stage heat. 
Once the rst stage prove switch is determined to be open, 
the combustion air inducer is energized on low (rst stage) 
heat  speed.  When  the  dierential  in  the  prove  switch  is 
great enough,  the  prove switch  closes and a  15-second 
pre-purge begins.