EasyManuals Logo

Lennox EL297DFV Series Unit Information

Lennox EL297DFV Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
Page 37
7. Combustion Air Inducer (B6) and
Cold End Header Box
All EL297DFV units use a two-stage combustion air induc-
er to move air through the burners and heat exchanger
during heating operation. The blower uses a 120VAC mo-
tor. The motor operates during all heating operation and
is controlled by integrated control A92. The inducer also
operates for 15 seconds before burner ignition (prepurge)
and for 5 seconds after the gas valve closes (postpurge).
The inducer operates on low speed during rst stage heat,
then switches to high speed for second stage heat.
NOTE - Each furnace model uses a unique CAI. Refer to
Lennox Repair Parts listing for correct inducer for replace-
ment.
The combustion air inducer is installed on the cold end
header box. The cold end header box is a single piece
made of hard plastic. The box has an internal channel
where the combustion air inducer creates negative pres-
sure at unit start up. The channel contains an orice used
to regulate ow created by the combustion air inducer.
The box has pressure taps for the combustion air induc-
er pressure switch hoses. The pressure switch measures
the pressure di󰀨erential across the combustion air inducer
orice or di󰀨erence in the channel and the box. If replace-
ment is necessary the gaskets used to seal the box to
the vestibule panel and the combustion air inducer to
the box, must also be replaced.
A proving switch connected to the combustion air inducer
orice plate is used to prove inducer operation. The com-
bustion air inducer orice will be di󰀨erent for each model.
See TABLE 14 for orice sizes. The pressure switch mea-
sures the pressure di󰀨erential across the combustion air
inducer orice. When the proving switch opens, the fur-
nace control (A92) immediately closes the gas valve to
prevent burner operation.
TABLE 14
EL297DFV Unit C.A.I. Orice Size
-045 0.650
-070 0.810
-090 0.920
-110 1.070
8. Combustion Air Inducer
Pressure Switch (S18)
EL297DFV(X) series units are equipped with a dual com-
bustion air pressure switch (rst and second stage) lo-
cated on the combustion air inducer orice bracket. See
FIGURE 16. The switch is connected to the combustion
air inducer housing by means of a exible silicone hose.
It monitors negative air pressure in the combustion air in-
ducer housing.
The switches are a single-pole single-throw pressure
switch electrically connected to the integrated control. The
purpose of the switch is to prevent burner operation if the
combustion air inducer is not operating or if the ue be-
comes obstructed.
On heat demand (rst or second stage) the switch senses
that the combustion air inducer is operating. It closes a
circuit to the integrated control when pressure inside the
combustion air inducer decreases to a certain set point.
Set points vary depending on unit size. See TABLE 15,
TABLE 16 and TABLE 17. The pressure sensed by the
switch is negative relative to atmospheric pressure. If
the ue becomes obstructed during operation, the switch
senses a loss of negative pressure becomes more equal
with atmospheric pressure) and opens the circuit to the
furnace control and gas valve. A bleed port on the switch
allows relatively dry air in the vestibule to purge switch
tubing, to prevent condensate build up.
COMBUSTION AIR PRESSURE SWITCH
3/16 Terminals
Low Fire Switch
High Fire Switch
1/4
" Terminals
Tap (negative - )
Tap (positive +)
FIGURE 16
TABLE 15
0 - 4500 ft
Unit Set Point High Heat Set Point Low Heat
-045 0.74 0.41
-070 0.90 0.50
-090 0.90 0.45
-110 1.00 0.55
TABLE 16
4501 - 7500 ft
Unit Set Point High Heat
Set Point Low
Heat
-045 0.74 0.41
-070 0.85 0.50
-090 0.75 0.45
-110 0.95 0.55
TABLE 17
7500 ft - 10,000 ft
Unit Set Point High Heat Set Point Low Heat
-045 0.70 0.40
-070 0.75 0.45
-090 0.70 0.40
-110 0.90 0.50

Other manuals for Lennox EL297DFV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox EL297DFV Series and is the answer not in the manual?

Lennox EL297DFV Series Specifications

General IconGeneral
BrandLennox
ModelEL297DFV Series
CategoryFurnace
LanguageEnglish

Related product manuals