LIST OF SETPOINTS
1st Level
Mini. Usine Maxi.
0 Password, level 1, numerical display unit 0 # 255
1 Temperature, required setpoint for room, day mode 8.0 21.0 35.0
2 Remote control, forced, occupied mode Off Off On
3 Remote control, forced, automatic mode Off Off On
4 Remote control, forced, unoccupied mode Off Off On
5 Fault reset Off Off On
6 Remote control, On / Off, unit Off Off On
7 Remote control, On / Off, customer Off Off On
8 Mode, Selection 0 0 7
0 = Day 1 = Week-end 2 = Night 3 =
4 = Morning 5 = Midday 6 = Evening 7 = BMS
9 Mode, Day of the week, start of mode 1 # 7
10 Mode, Hour, start of mode 0 # 23
11 Mode, Minute, start of mode 0 # 59
12 Mode, Day of the week, end of mode 1 # 7
13 Mode, Hour, end of mode 0 # 23
14 Mode, Minute, end of mode 0 # 59
15 Mode, Temperature, Room Heating Setpoint, 8.0 # 35.0
16 Mode, Temperature, Room Cooling Setpoint, 8.0 # 35.0
17 On = Absolute humidity (g/kg) / Off = Relative humidity (%) Off Off On
18 Mode, Relative humidity (%),
Room Minimum setpoint required 0 # 100
19 Room Mode, Relative humidity (%),
Maximum setpoint required 0 # 100
20 Mode, Absolute humidity (g/Kg),
Room Minimum setpoint required 0.0 # 30.0
21 Mode, Absolute humidity (g/Kg),
Room Maximum setpoint required 0.0 # 30.0
22 Mode, Percentage, Minimum fresh air 0 # 100
23 Mode, Fan activity, control zone Off # On
24 Mode, Fan activity, dead zone Off # On
25 Mode, Fan automation, dead zone Off # On
26 Mode, Fan low speed, control zone Off # On
27 Mode, Fan low speed, dead zone Off # On
28 Mode, Fan low speed automation Off # On
29 Remote control, Forced, Mode Off Off On
30 Remote control, Forced, Low fan speed Off Off On
31 Remote control, Forced damper with recycled air Off Off On
32 Remote control, Forced damper with minimum fresh air Off Off On
33 Remote control, Forced damper with fresh air Off Off On
34 Remote control, Forced 50% load limit Off Off On
35 Remote control, Forced heating cancellation Off Off On
36 Remote control, Forced cooling cancellation Off Off On
37 On = Electrical heaters during defrosting Off On On
38 Room Temperature, Low setpoint 5.0 10.0 20.0
39 Room Temperature, High setpoint 20.0 40.0 40.0