Page 38 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAUSING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLAUSING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
YY
YY
Y
40 Room Relative humidity (%), Low setpoint 0 0 50
41 Room Relative humidity (%), High setpoint 50 100 100
42 Room Absolute humidity (g/Kg), Low setpoint 0.0 0.0 30.0
43 Room Absolute humidity (g/Kg), High setpoint 0.0 30.0 30.0
44 Temperature, Curved gradient of anticipated speed 0.0 10.0 20.0
45 Value, Gradient of anticipated speed 0 12 100
46 Ppm, Curved gradient, Minimum fresh air / CO² 0 1000 2000
47 Value, Gradient, Minimum fresh air / CO² 0 1500 2000
48 Absolute humidity (g/kg), enthalpy room setpoint 0.0 10.0 50.0
49 Percentage, Fresh air opening, Exhaust Damper 0 10 100
2nd Level
Mini. Usine Maxi.
50 Time, Sampling room setting 1 10 120
51 Differential temperature, Engaged heat setting 0.0 1.0 10.0
52 Differential temperature, Heating setting between 2 steps 0.1 1.0 10.0
53 Differential temperature, Engaged cooling setting 0.0 1.0 10.0
54 Differential temperature, Cold setting between 2 steps 0.1 1.0 10.0
55 On = Compressors then V3V EG, room setting Off Off On
56 On = PAC and/or Gas then V3V BEC or Elec.,
Room setting Off Off On
57 On = Gas then heat pump, Room setting Off Off On
58 On = Supply setting On Off Off On
59 Time, Sampling of supply setting 1 10 120
60 On = Heat pump and/or Gas then V3V BEC or Elec,
Supply setting Off Off On
61 On = Gas then heat pump, Supply setting Off Off On
62 On = Louver levelling setting On Off Off On
63 On = Compressors then V3V EG, Supply setting Off Off On
64 Time, Sampling of humidity setting 1 10 120
65 Humidity range (%), Humidity setting 1 5 50
66 Differential humidity (%), Engaged dehumidity setting 1 5 50
67 Differential humidity (%), Dehumidity setting between 2 steps 1 5 50
68 SupplyTemperature, Low setpoint, 1st level n.2 + 2.0 8.0 19.0
69 SupplyTemperature, Low setpoint, 2nd level n.3 + 2.0 6.0 17.0
70 Supply Temperature, Low setpoint, 3rd level 1.0 2.0 15.0
71 SupplyTemperature, High setpoint, 1st level 20.0 40.0 70.0
72 SupplyTemperature, High setpoint, 2nd level n.1 60.0 70.0
73 Temperature, Outside Air minimum setpoint, 0.0 5.0 30.0
74 Temperature, Outside Air maximum setpoint, 0.0 26.0 60.0
75 Percentage, Maximum fresh air, Louver levelling 0 60 100
76 Outside Air Temperature, setpoint,
50% Compressor discharge 10.0 24.0 30.0
77 Outside Air Temperature, setpoint,
100% Compressor discharge 10.0 12.0 30.0
78 Icing Temperature Setpoint -5.0 -1.0 3.0
79 Defrost Temperature, setpoint, Compressor battery 5.0 10.0 15.0
80 Outside Temperature, setpoint, Discharge 100% heat pump -50.0 -20.0 20.0
81 Outside Temperature, setpoint, Authorised defrosting 8.0 10.0 20.0