IS 24VAC ACROSS
J73
PIN 11 AND 1
OF VSP1?
V" BLOWER AND VSP1 BLOWER CONTROL BOARD
HEATING MODE CHECKOUT
NO
DOES UNIT OPERATE?
YES
NO
YES
YES
CHECK VOLTAGE ON TB2 FROM ACC TO N ON TERMINAL
BLOCK INSIDE CONTROL BOX−SHOULD READ "120" VOLTS AC
CHECK UNIT WIRING FROM
VSP1 TO TB2 AND IF CORRECT,
REPLACE VSP1.
DS3 DS2 DS1
PLACE JUMPER ACROSS R AND W1.
WAIT 75 SECONDS FOR PREPURGE AND FANON DELAY.
CHECK OUT ELECTRONICALLY CONTROLLED BLOWER MOTOR AND
VSP1
SEE SECTION VIIINEW UNIT STARTUP
IS 24VAC ACROSS R AND C ?
YES
IS 24VAC ACROSS
PIN 8 AND 1
OF VSP1?
NO
CHECK:
1−UNIT POWER
2−INTERLOCK SWITCH
3−TRANSFORMER
4−TRANSFORMER FUSE
5−UNIT WIRING
IS 24VAC ACROSS J73
PIN 7 AND 1
OF VSP1?
NO
PRIMARY LIMIT S10 IS NC
ALLOW UNIT TO COOL
IF LIMIT REMAINS OPEN
REPLACE LIMIT
YES
IS 24VAC ACROSS J73
PIN 3 AND 1
OF VSP1?
NO REPLACE VSP1
YES
NO
CHECK WIRING BETWEEN TB1 AND VSP1
REPAIR IF NECESSARY
YES
IS 24VAC ACROSS J73
PIN 10 AND 1
OF VSP1?
NO
REPLACE VSP1
YES
IS BLOWER ON LOW SPEED
AND IS DS1 LIT?
BREAK AND RE
MAKE
JUMPER (R TO W1).
YES
NO
S78 IS A NC LIMIT
ALLOW UNIT TO COOL
IF LIMIT REMAINS
OPEN REPLACE
LIMIT
YES
IF UNIT DOES NOT OPERATE
THE GAS VALVE OR IGNI
TION CONTROL ARE NOT
OPERATING PROPERLY
IS THE ACCESSORY
RELAY PULLED IN?
CONTINUED ON FOLLOWING PAGE
TB2
ACC N
120VAC?
DS3 DS2 DS1
L1
ACC
NO
1
3
6912
J73
J73
1
START HERE
1
VSP1

Table of Contents

Other manuals for Lennox G21Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G21Q Series and is the answer not in the manual?

Lennox G21Q Series Specifications

General IconGeneral
BrandLennox
ModelG21Q Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals