8 - ELECTRICAL CONNECTIONS
8.8 Management of 0-10V Input
P78=1 P78 = 2
0-10V DC Electrical Signal Input Heating Flow Setpoint Temperature Central Heating - Heat Input (Gross)
(V) (°F) (°C)
150 205
(kW) (Btu/h) (kW) (Btu/h)
0...3 OFF
3 77 25 6.4 22,000 8.6 29,500
4 95 35 10.8 36,700 14.2 48,620
5 108 42 15.1 51,400 19.9 67,740
6 124 51 19.4 66,100 25.5 86,860
7 140 60 23.7 80,800 31.1 105,980
8 154 68 28.0 95,500 36.7 125,100
9 167 75 32.3 110,200 42.3 144,220
10 176 80 36.6 125,000 48.1 164,000
The functions with 0...10V regulator are activated by means of their parameters. When the function is enabled (P82=3)
and P78=1, the input manages the heating set point temperature directly; when P78=2, the input manages the heating
power input directly. Demand is activated above 3V and the heating setpoint is calculated in proportion to deviation from 3
to 10 V DC, to give a setpoint that goes from minimum to maximum.