EasyManuals Logo
Home>Lennox>Control Systems>Harmony II Zone Control System

Lennox Harmony II Zone Control System User Manual

Lennox Harmony II Zone Control System
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Page 7
System Components
Harmony
®
II Control Components
Control Panel (Figure 1)The user selects the mode of
operation on the Harmony
®
II control panel. Raised but-
tons and corresponding LEDs for each mode are on the
control panel.
Control Center (Figure 2)The control center is thebrain"
of the zone control system. The control organizes the opera-
tion of the thermostats, dampers, and HVAC equipment for to-
tal comfort.
Other System Components (Ordered Separately)
ThermostatsThermostats are required for each zone and
may be programmable or conventional but must have a dead
band between HEAT and COOL. In Central Control mode, the
zone 1 thermostat is designated as the master thermostat.
The other thermostats are not used. In the Zone Control
mode, the unused zones are referred to as zone 2, zone 3,
and zone 4.
Dampers and Damper TransformerMotorized damp-
ers are used in the supply duct system to allow air distribu-
tion to the zones. The dampers use 24VAC to close and
spring−return to open.
The dampers are powered by a separate, field−provided
24VAC transformer. The transformer must have an ade-
quate VA rating for the number of operating dampers.
Discharge Air Temperature ProbeA discharge air tem-
perature probe or sensor monitors the supply air. This
probe gathers temperature information across the air
stream. It is not a limit switch.
Pressure SwitchA pressure switch is required for ap-
plications with a Lennox heat pump (Options 2 and 3). The
pressure switch acts as a safety device in case of high
head pressures during first− and second−stage heating.
Temperature Modulation SwitchWhen applying the
Harmony
®
II zone control system to the G32V furnace (op-
tions 1 and 3), you must install a temperature modulation
switch. The switch senses the temperature of the supply
air. Based on that air temperature, the switch will allow the
gas valve to change from high fire to low fire or from low fire
to high fire. The normally closed switch (72 H45) is not sup-
plied with the zoning control or with the furnace and must
be ordered separately.
Harmony
®
II Control Panel
Figure 1
Harmony
®
II Control Center
or Gas
or Gas
Discharge/
Bypass But-
ton
Figure 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Harmony II Zone Control System and is the answer not in the manual?

Lennox Harmony II Zone Control System Specifications

General IconGeneral
BrandLennox
ModelHarmony II Zone Control System
CategoryControl Systems
LanguageEnglish

Related product manuals