Variable cOndensinG unit minimum Heat PumP HeatinG cFm
Table 34. Variable Condensing Unit Minimum Heat Pump Heating CFM
(Maximum pressure approximately @525PSI)
Model EL18XPV-024 EL18XPV-036 EL18XPV-048 EL18XPV-060
System at Minimum Capacity .875 Tons .86 Tons 1.6 Tons 1.78 Tons
Minimum CFM @380 CFM Per Ton
For Zoning
333 CFM 327 CFM 608 CFM 677 CFM
Recommend CFM @450 CFM Per
Ton
394 CFM 387 CFM 720 CFM 801 CFM
electric HeatinG ecba25-P / cba25uHV
Table 35. Electric Heating ECBA25-P / CBA25UHV
(@240VAC 3.413 BTU per Watt)
Size by kW No. Of Stages LowHeatingBTU Airowto30°Tr Max Heating BTU
4kW 1 13,652 421 CFM 13,652
5kW 1 17,065 527 CFM 17,065
7.5kW 1 25,598 790 CFM 25,598
10kW 1 34,130 1053 CFM 34,130
12.5kW 2 28,441 878 CFM 42,662
15kW 2 34,130 1053 CFM 51,195
20kW 2 34,130 1053 CFM 68,260