Page 30
IV-CHARGING
A-All Aluminum Outdoor Coil
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
       
any condition.
This unit is factory charged and should require no further
    
reclaim the chargeevacuate the systemadd required
nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C), the charge
must be weighed into the system.
         

IMPORTANT - Charge unit in standard cooling mode.
1 - Make sure outdoor coil is clean. Attach gauge
        
mode with economizer disabled until system
  
all outdoor air dampers are closed.
2 - Check each system separately with all stages
operating. Compare the normal operating pressures

obtained from the gauges. Check unit components
󰀨
3 - Measure the outdoor ambient temperature and
      
circuit charging curve to determine a target liquid
temperature.
NOTE - Pressures are listed for sea level
applications.
4 - Use the same thermometer to accurately measure

If measured liquid temperature is higher than the

system.
If measured liquid temperature is lower than the
-
ant from the system.
 Add or remove charge in increments. Allow the
system to stabilize each time refrigerant is added
or removed.
6 - Continue the process until measured liquid
temperature agrees with the target liquid
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
7 -        
ambient and a measured suction pressure of


in increments until measured liquid temperature
agrees with the target liquid temperature.