TABLE 11 581126-01
KG/KC 102S Normal Operating Pressures - All-Aluminum Coil
Outdoor Coil Entering Air Temperature
65°F 75°F 85°F 95°F 105°F 115°F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
100  103 288 106 337 109 390 112 449  
107  110 293 113 340 117 392 120  123 
122 262 126 301 130  134  138  141 
140 271 144 307 149 349  396  448 162 
Circuit 2
110 262 113 300  342 118 388 121 439 124 493
117 267 120 306 123 348 127 394 130  133 499
130 278 134 317 138  143 406 147   
142 288 148 327  371  418 163 468 168 
60
70
80
90
100
110
120
130
95 105 115 125 135145 155
Liquid Temperature (F)
Suction Pressure (psig)
Outdoor Temperature (°F)
115°
105°
95°
85°
75°
65°
102S Charging Curves - All-Aluminum Coil
Circuit 1
Circuit 2
165