B-Refrigerant Charge and Check - Fin/Tube Coil
       
any condition.
This unit is factory charged and should require no further
    

nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
         

IMPORTANT - Charge unit in standard cooling mode.
1 - Attach gauge manifolds and operate unit in cool-
ing mode with economizer disabled until system

outdoor air dampers are closed.
2 - Check each system separately with all stages
operating.
3 - Use a thermometer to accurately measure the out-
door ambient temperature.
4 - Apply the outdoor temperature to TABLE 14 to
TABLE 17 to determine normal operating pressures.
Pressures are listed for sea level applications at

 Compare the normal operating pressures to the
pressures obtained from the gauges. Minor varia-
tions in these pressures may be expected due to
󰀨󰀨
could mean that the system is not properly charged
or that a problem exists with some component in
the system. Correct any system problems before
proceeding.
6 - 

refrigerant to the system.
Add or remove charge in increments.
Allow the system to stabilize each time refriger-
ant is added or removed.
7 - Use the following approach method along with the

TABLE 14 581129-01
KGC/KCC092S Fin/Tube - W & W/O Reheat
Outdoor
Coil
Entering
Air Temp
CIRCUIT 1 CIRCUIT 2
Discharge
+ 10 psig
Suction +
5 psig
Discharge
+ 10 psig
Suction +
5 psig
 270 128  140
 310 131  146
  133 338 
 401 136 388 
  140 433 160
   488 162
TABLE 15 581130-01
KGC/KCC102S Fin/Tube - W & W/O Reheat
Outdoor
Coil
Entering
Air Temp
CIRCUIT 1 CIRCUIT 2
Discharge
+ 10 psig
Suction +
5 psig
Discharge
+ 10 psig
Suction +
5 psig
 269 128 276 138
 308 132 314 142
    146
 396 139 407 149
 447 141  
  146  