5-High Altitude


6-Proper Gas Flow




19. Seconds in TABLE 19 are based on a 1 cu.ft. dial

LP. Adjust manifold pressure on gas valve to match time
needed.
NOTE - To obtain accurate reading, shut o all other gas
appliances connected to meter.
TABLE 19
 Seconds for
Natural
Seconds for
Propane
 43 106
 31 77
 28 69
 23 
 20 
  37


1 - 󰀨
2 - 
3 - 
4 - 
Pay careful attention to the order in which gaskets

      

6 - 
7 -       
sure to secure all wires and check plumbing and
burner plate for airtight seal. Screws must be

8-Flame Sensing

the ignition control through the sensor electrode during
unit operation. The current passes from the sensor through
       
       

        
       
following page:
CAUTION

to the electrode may create a hazardous condition
that can cause property damage or personal injury.
1 - Disconnect power to unit.
2 -       
       
sensing electrode and the sensing lead.
3 - 
demand.
4 -      
        
Dropout signal is .09 or less.
 Disconnect power to unit before disconnecting
meter. Make sure sensor wire is securely
reconnected before reconnecting power to unit.
NOTE-If the meter scale reads 0, the leads are
reversed. Disconnect power and reconnect leads for
proper polarity.
B-Cooling System Service Checks
KGC units are factory charged and require no further
     
periodically using the approach method. The approach
method compares actual liquid temperature with the

NOTE - When unit is properly charged, discharge line
pressures should approximate those in TABLE 10 through
TABLE 17.