TABLE 8 581126-01
KG/KC 102S Normal Operating Pressures - All-Aluminum Coil
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
STG 1
100 245 103 288 106 337 109 390 112 449 115 513
107 251 110 293 113 340 117 392 120 450 123 513
122 262 126 301 130 345 134 395 138 450 141 510
140 271 144 307 149 349 153 396 158 448 162 506
STG 2
110 262 113 300 115 342 118 388 121 439 124 493
117 267 120 306 123 348 127 394 130 445 133 499
130 278 134 317 138 359 143 406 147 457 151 511
142 288 148 327 153 371 158 418 163 468 168 523
60
70
80
90
100
110
120
130
95 105 115 125 135 145 155
Liquid Temperature ( F)
Suction Pressure (psig)
Outdoor Temperature (°F)
115°
105°
95°
85°
75°
65°
102S Charging Curves - All-Aluminum Coil
Circuit 1
Circuit 2
165