5-Flame Rollout Limits S47, S69

second heat section are SPST N.C. high temperature
limits located just above the burner air intake opening in
       



the ignition control immediately closes the gas valve. Limit

open at 250 F + 12 F (121.1 C + 6.7 C) on a temperature
rise, while on high heat units both limits open at 270 F +
-
out limits are manual reset.
6-Combustion Air Prove Switches S18, S45

heat section) are located in the compressor compartment.
Both are identical SPST N.O. switches and monitor com-
bustion air inducer operation. Switch S18 and S45 are
wired to the A55 Unit Controller.
The switch closes on a negative pressure fall. This nega-
tive pressure fall and switch actuation allows the ignition
sequence to continue (proves, by closing, that the com-
bustion air inducer is operating before allowing the gas
valve to open.) The combustion air prove switch is factory
set and not adjustable. The switch will automatically open

prove switch settings.
TABLE 9
S18 & S45 Prove Switch Settings
Close“ w.c. (Pa) Open “ w.c. (Pa)
0.25 + 5 (62.3+12.4) 0.10+5 (24.8+12.4)
7-Combustion Air Inducers B6 & B15
   
B15 on the second heat section, are identical blowers
which provide fresh air to the corresponding burners while
clearing the combustion chamber of exhaust gases. The
blowers begin operating immediately upon receiving a
thermostat demand and are de-energized immediately

Both combustion air blowers use a 208/230 or 460V sin-
glephase PSC motor and a 4.81in. x 1.25in. (122mm x
32mm) blower wheel. All motors operate at 3200 or 3450
RPM and are equipped with auto-reset overload protec-
tion. Blowers are supplied by various manufacturers. Rat-

ratings can be found on the unit rating plate.
All combustion air blower motors are sealed and cannot
be oiled. The blower cannot be adjusted but can be disas-
sembled for cleaning.
8-Combustion Air Motor Capacitors C3 & C11
The combustion air blower motors in all LGH units require
run capacitors. Capacitor C3 is connected to combustion
air blower B6 and C11 is connected to combustion air
blower B15. Both capacitors are rated at 3 or 4 MFD for
208/230 CAB and 4 MFD for 460V CAB.
9-Gas Valves GV1 & GV3
Gas valves GV1 and GV3 are identical. The gas valves
are two-stage redundant valves. Units are equipped with
      
󰀨
seconds). On the Honeywell second stage is quick open-
ing.
-
gized by the ignition control simultaneously with the spark

second stage operator is energized directly from A55
(GV1, GV3). The Honeywell valve is adjustable for both
󰀨
󰀨󰀨-
ly closes both stages without delay. Figure 23 shows gas
valve components.
Table 10 shows factory gas valve regulation for LGH se-
ries units. Optional factory installed gas valves for single
stage heat only, are available for the LGH156, 180 and
210. Gas valves are wired without W2 eliminating two
stage heat.
LOW FIRE
ADJUSTMENT
HIGH FIRE
ADJUSTMENT
INLET
PRESSURE
TAP
MANIFOLD
PRESSURE
TAP
GAS VALVE
GAS VALVE SHOWN IN “OFF” POSITION
FIGURE 23
TABLE 10
GAS VALVE REGULATION FOR LGM UNITS
Operating Pressure (outlet) Factory Setting
Natural LP
Low High Low High
1.6+0.2”WC

3.7+0.3”WC

5.5+0.3”WC
1368+75Pa
10.5+0.5”WC
2611+7124Pa
The maximum inlet pressure is 13.0” WC (3232PA)