LGH SERIES
Service Literature
7.5 to 12.5 ton
38.1 to 70.3 kW
Revised 05/2020
LGH092H through 152U
The LGH092H, 094U, 102H, 120H, 122U, 150S, 150H
and 152U units are configure to order units (CTO) with a
wide selection of factory-installed options. Units are
available in 130,000, 180,000 Btuh or 240,000 Btuh
(38.1, 52.7 or 70.3 kW) heating inputs. Gas heat sec
tions are designed with aluminized steel tube heat ex
changers with stainless steel as an option.
Cooling capacities range from 7.5 to 12.5 tons (38.1 to
70.3 kW). All units are equipped with two compressors.
Ultra-high efficiency units are available with an optional di
rect drive blower or belt drive blower equipped with a sup
ply air inverter. Standard and high efficiency units are
available with a belt drive blower equipped with an option
al supply air inverter. The blower will operate at lower
speeds when demand is low and increase to higher
speeds when demand is high.
The following examples show the model numbers of ten-
ton units with all available blower options:
LGH120H4B High Efficiency Belt Drive
LGH120H4M High Efficiency Belt Drive with Inverter
LGH122U4M Ultra High Efficiency Belt Drive with Inverter
LGH122U4E Ultra High Efficiency Direct Drive
Note - Ten-ton units are available in high and ultra high effi
ciencies only.
Standard and high efficiency units come standard with a
lightweight, all-aluminum condenser coil; optional, fin/
tube condenser coils are available. Ultra-high efficiency
units come standard with a tube/fin condenser coil.
Ultra high efficiency units come standard with two single-
speed compressors plumbed in tandem to form a single re
frigerant circuit.
Units are also designed for R410A refrigerant. See unit
nameplate. Operating pressures and pressure switch set
tings are significantly higher than R22 charged units. Ser
vice equipment must be rated for R410A.
Standard and high efficiency units offer mechanical cooling
down to 0°F when properly equipped. Ultra-high efficiency
units offer mechanical cooling down to 40°F.
All LGH units are designed to accept any of several differ
ent energy management thermostat control systems with
minimum field wiring. Factory or field provided control op
tions connect to the unit with jack plugs. When ”plugged in”
the controls become an integral part of the unit wiring.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the
proper rigging technique.
3
3
Table of Contents
Options / Accessories Page 2.....................
Specifications Page 8............................
Blower Tables Page 14............................
Electrical Data Page 19...........................
Parts Arrangement Page 25.......................
I-Unit Components Page 28.......................
II-Placement and Installation Page 47...............
III-Charging Page 47..............................
IV-Start Up - Operation Page 55....................
V-System Service Checks Page 57................
High Altitude Page 59.........................
VI-Maintenance Page 59..........................
VII-Accessories Page 60..........................
VIII-Belt Drive Supply Air Inverter Page 67...........
IX-Direct Drive Supply Air Blower Page 70...........
X-Staged Supply Air Operation Page 71.............
XI-Wiring and Operation Sequence Page 72.........
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property va, personal in
jury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer
or equivalent, service agency, or the gas supplier
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
© 2019

Other manuals for Lennox LGH094U

Question and Answer IconNeed help?

Do you have a question about the Lennox LGH094U and is the answer not in the manual?

Lennox LGH094U Specifications

General IconGeneral
BrandLennox
ModelLGH094U
CategoryAir Conditioner
LanguageEnglish

Summary

Service Literature

LGH092 H through 152 U Series

Details LGH092H through 152U unit series features, heating inputs, cooling capacities, and compressor configurations.

General Safety Warnings

Warns about improper installation, adjustment, alteration, service, or maintenance causing injury or death.

Handling Precautions

Advises caution when handling equipment due to sharp sheet metal edges.

Options and Accessories

Cooling System Options

Lists available options and accessories for the cooling system.

Heating System Options

Lists available options and accessories for the heating system.

Supply Air Blower Options

Details available supply air blower options and related accessories.

Cabinet Accessories

Lists cabinet-related accessories like combination coil/hail guards.

Additional Options and Accessories

Control Options

Lists various control options and accessories for the unit.

Indoor Air Quality Options

Details options related to indoor air quality, including filters and sensors.

Electrical Options

Lists electrical options like voltage and circuit breakers.

Economizer and Air Management Options

Economizer Options

Details standard and high-performance economizer options and controls.

Outdoor Air Damper Options

Lists options for outdoor air dampers.

Power Exhaust Option

Describes the standard static power exhaust option.

Humiditrol Condenser Reheat Option

Details the Humiditrol option for condenser reheat.

Model Specific Options (094 U, 122 U, 152 U)

Cooling System Options by Model

Lists cooling system options for specific models.

Heating System Options by Model

Lists heating system options for specific models.

Supply Air Blower Options by Model

Details supply air blower options for specific models.

Model Specific Options (094 U, 122 U, 152 U) - Part 2

Cabinet Accessories by Model

Lists cabinet accessories for specific models.

Control Options by Model

Details control options for specific models.

Indoor Air Quality Options by Model

Lists indoor air quality options for specific models.

Model Specific Options (094 U, 122 U, 152 U) - Part 3

Economizer Options by Model

Describes economizer options for specific models.

Outdoor Air Options by Model

Lists outdoor air damper options for specific models.

Power Exhaust Option by Model

Details the power exhaust option for specific models.

Specifications - 092 H, 102 H Models

General Data

Provides general data for 7.5 and 8.5 ton models.

Cooling Performance

Details cooling performance metrics like capacity, airflow, and efficiency.

Refrigerant Charge

Lists refrigerant type and charge amounts for different coil options.

Gas Heating Options

Indicates availability of gas heating options.

Specifications - 120 H, 150 H Models

General Data

Provides general data for 10 and 12.5 ton models.

Cooling Performance

Details cooling performance metrics like capacity, airflow, and efficiency.

Refrigerant Charge

Lists refrigerant type and charge amounts for different coil options.

Specifications - Gas Heat (092 H, 102 H, 120 H, 150 H)

Gas Heating Performance

Details gas heating performance, including input, output, and efficiency.

High Altitude Derate

Provides information on derating units for high altitude installations.

Specifications - Direct Drive Models

General Data

Provides general data for direct drive models.

Cooling Performance

Details cooling performance metrics for direct drive models.

Refrigerant Charge

Lists refrigerant type and charge for direct drive models.

Specifications - Belt Drive Models (094 U, 122 U, 152 U)

General Data

Provides general data for belt drive models.

Cooling Performance

Details cooling performance for belt drive models.

Refrigerant Charge

Lists refrigerant type and charge for belt drive models.

Specifications - Gas Heat (094 U, 122 U, 152 U)

Gas Heating Performance

Details gas heating performance for specific models.

Blower Data - Base Unit

092, 094, 102 Belt Drive Blower Data

Blower data for base units, excluding heat section.

Maximum Static Pressure with Gas Heat

Specifies the maximum static pressure with gas heat.

Blower Data - Base Unit (Continued)

120, 122, 150, 152 Belt Drive Blower Data

Blower data for base units, excluding heat section.

Maximum Static Pressure with Gas Heat

Specifies the maximum static pressure with gas heat.

Blower Data - Unit Options

Factory Installed Belt Drive Kit Specifications

Details specifications for factory-installed belt drive kits.

Power Exhaust Fan Performance

Provides performance data for the power exhaust fan.

Accessory Air Resistance

Lists air resistance values for factory/field installed options.

Blower Data - Diffuser Information

Ceiling Diffusers Air Resistance

Provides air resistance data for ceiling diffusers.

Ceiling Diffuser Air Throw Data

Details air throw data for ceiling diffusers.

Blower Data - Direct Drive

Maximum Static Pressure with Gas Heat

Specifies the maximum static pressure with gas heat.

Electrical Data - High Efficiency

7.5 Ton High Efficiency (R-410 A)

Electrical data for 7.5 ton high efficiency units.

8.5 Ton High Efficiency (R-410 A)

Electrical data for 8.5 ton high efficiency units.

Electrical Data - High Efficiency (Continued)

10 Ton High Efficiency (R-410 A)

Electrical data for 10 ton high efficiency units.

12.5 Ton High Efficiency (R-410 A)

Electrical data for 12.5 ton high efficiency units.

Electrical Data - Direct Drive

7.5 Ton Direct Drive

Electrical data for 7.5 ton direct drive models.

Electrical Data - Direct Drive (Continued)

12.5 Ton Direct Drive

Electrical data for 12.5 ton direct drive models.

Electrical Data - Belt Drive

7.5 Ton Belt Drive

Electrical data for 7.5 ton belt drive models.

Electrical Data - Belt Drive (Continued)

10 Ton Belt Drive

Electrical data for 10 ton belt drive models.

Parts Arrangement Diagrams

All-Aluminum Coil System

Shows the physical arrangement of parts for the all-aluminum coil system.

FinTube Coil System

Shows the physical arrangement of parts for the fin/tube coil system.

Control Box Parts Arrangement

Standard and High Efficiency Non-CE Units

Details the arrangement of components within the control box for non-CE units.

Control Box Parts Arrangement - Unit Types

Ultra High Efficiency Non-CE Units

Shows layout of control box for ultra high efficiency non-CE units.

CE Units

Illustrates control box components for CE certified units.

Unit Components - Control Box

Control Box Components Overview

Overview of control box components and ESD precautions.

Disconnect Switch S48 (Optional)

Describes the optional disconnect switch used to power down the unit.

Control Transformer T1

Explains the function and specifications of the control transformer.

Outdoor Fan Relays K10, K68

Details the function of outdoor fan relays.

Unit Components - Various

Burner Controls A3

Describes the function of burner controls.

Power Exhaust Relay K65

Explains the function of the power exhaust relay.

Blower Motor Overload Relay S42

Details the blower motor overload relay and its operation.

Unit Controller A55

Describes the functions and capabilities of the Unit Controller.

Unit Components - Optional Features

Compressor Overload Relays S176, S177

Explains compressor overload relays for CE units.

Variable Frequency Drive A96 (Optional)

Describes the variable frequency drive and its operation.

VFD Power To Motor Contactor K202

Details the VFD power to motor contactor.

Inverter Start Forward Rotation Relay K203

Explains the inverter start forward rotation relay.

Refrigerant Circuit Diagrams

High Efficiency All-Aluminum Outdoor Coil

Illustrates plumbing and refrigerant circuits for high efficiency units with all-aluminum coils.

Refrigerant Circuit Diagrams - Continued

Optional Standard Efficiency FinTube Coil

Shows plumbing and refrigerant circuits for standard efficiency fin/tube coil units.

Refrigerant Circuit Diagrams - Ultra High Efficiency

Optional Ultra High Efficiency Units with FinTube Coil

Illustrates plumbing and refrigerant circuits for ultra high efficiency units with fin/tube coils.

Cooling Components Overview

Compressors B1, B2

Describes the compressors and their circuits.

Crankcase Heaters HR1, HR2

Details the function and installation of crankcase heaters.

High Pressure Switches S4, S7

Explains the operation of high-pressure switches.

Cooling Components - Switches and Sensors

Low Ambient Switches S11, S84

Describes the function of low ambient switches.

Service Valve (Optional)

Mentions optional service valves for condenser units.

Filter Drier

Explains the purpose of the filter drier in refrigerant circuits.

Low Pressure Switches S87, S88

Details the operation of low-pressure switches.

Cooling Components - Sensors and Controls

Freezestats S49 and S50

Describes the function of freezestats to prevent coil icing.

Temperature Sensors RT37 and RT38

Explains the use of temperature sensors for system optimization.

Pressure Transducer A185

Details the function of the pressure transducer for system optimization.

Blower Assembly Diagrams

Standard Blower Assembly

Illustrates the standard blower assembly.

Tensioner Blower Assembly

Shows a tensioner blower assembly without the belt.

Blower Compartment and Operation

Direct Drive Blower Assembly

Illustrates the direct drive blower assembly.

Blower Compartment Access

Describes the location and access to the blower compartment.

Servicing Belt Drive Blowers

Provides instructions for servicing belt drive blowers.

Servicing Direct Drive Blowers

Gives servicing instructions for direct drive blowers.

Unit Operation and Adjustment

Determining Unit Air Volume

Explains how to determine unit air volume and adjust CFM.

Four Phase Scroll Compressor Voltage Phasing

Details importance of correct voltage phasing for compressor rotation.

Blower Belt Adjustment and Alignment

Static Pressure Reading Locations

Shows locations for static pressure readings for ductwork and diffusers.

Pulley Alignment

Illustrates correct pulley alignment for belt drives.

Belt Tension Check

Measuring Belt Tension

Describes how to measure belt tension using force and deflection.

Field-Furnished Blower Drives

Information on field-furnished blower drives and table of drive components.

Gas Heat Components - Ignition

Burner Ignition Control A3

Explains the function and operation of the burner ignition control.

Normal Ignition Sequence Timings

Diagram showing the nominal timings for a normal ignition sequence.

Ignition Attempt Sequence Timings

Diagram illustrating ignition attempt sequence with retrials.

Gas Heat Components - Heat Exchanger and Burners

Heat Exchanger Details

Describes the heat exchanger assembly and its operation.

Gas Heat Exchanger Inserts

Details inserts for direct drive heat exchangers.

Burner Assembly

Explains the burner assembly and its control.

Gas Heat Components - Burner Parts

Insert Location - Direct Drive Only

Shows insert locations for direct drive units.

Primary High Temperature Limits S10

Details the function of the primary high temperature limit switch.

Orifice Function and Installation

Explains the function and installation of burner orifices.

Gas Heat Components - Safety and Controls

Flame Roll-out Limit S47

Describes the flame roll-out limit switch and its function.

Combustion Air Prove Switch S18

Explains the combustion air prove switch operation.

Combustion Air Inducer B6

Details the combustion air inducer and its motor.

Combustion Air Motor Capacitor C3

Specifies the capacitor for the combustion air inducer motor.

Gas Valve and Spark Electrode Information

White-Rodgers 36 C76 Gas Valve

Illustrates the White-Rodgers gas valve and its adjustments.

Honeywell VR8305 VR8205 Gas Valve

Shows the Honeywell gas valve and its adjustments.

Spark Electrodes

Describes the spark electrode assembly and its function for ignition.

Refrigerant Charging Procedure (All-Aluminum Coil)

Refrigerant Charge and Check

Procedure for refrigerant charge and check for all-aluminum coil units.

Charging Example Circuit 1

Example of calculating target liquid temperature for charging.

Refrigerant Charging Curves (All-Aluminum Coil)

LGHLCH092 H4 Charging Curves

Charging curves for LGH/LCH092H4 all-aluminum TXV units.

LGHLCH102 H Charging Curves

Charging curves for LGH/LCH102H all-aluminum TXV units.

Refrigerant Charging Curves (All-Aluminum Coil) - Continued

LGHLCH120 H Charging Curves

Charging curves for LGH/LCH120H all-aluminum coil units.

LGHLCH150 S Charging Curves

Charging curves for LGH/LCH150S all-aluminum coil units.

Refrigerant Charging Procedure (FinTube Coil)

Refrigerant Charge and Check (FinTube Coil - TXV)

Procedure for refrigerant charge and check for fin/tube coil TXV units.

Refrigerant Charge and Check (FinTube Coil Hot Gas Reheat - TXV)

Procedure for fin/tube coil hot gas reheat TXV units.

Refrigerant Charging Procedure (FinTube Coil) - Part 2

Refrigerant Charge and Check (FinTube Coil & RFC)

Procedure for fin/tube coil & RFC refrigerant charge and check.

Refrigerant Pressures and Charging Curves (FinTube Coil)

LGHLCH150 S Operating Pressures

Operating pressures for LGH/LCH150S fin/tube RFC units.

LGHLCH150 S Charging Curves

Charging curves for LGH/LCH150S RFC fin/tube units.

Refrigerant Charge and Check (FinTube Coil & TXV) - Part 3

Refrigerant Charge and Check (FinTube Coil & TXV)

Procedure for fin/tube coil & TXV refrigerant charge and check.

Approach Temperature Table

Table for approach temperature verification.

Start-Up and Operation Procedures

Preliminary and Seasonal Checks

Steps for preliminary and seasonal checks before unit operation.

Cooling Start-up

Instructions for starting up the cooling system.

Heating Start-up Procedures

Placing Furnace In Operation

Steps for placing the furnace into operation.

Turning Off Gas to Appliance

Instructions for safely turning off gas to the appliance.

Safety or Emergency Shutdown

Steps for safety or emergency shutdown of the unit.

System Service Checks - Heating

Heating System Service Checks

Procedures for performing heating system service checks.

Gas Piping Guidelines

Guidelines for gas piping installation and testing.

Testing Gas Piping

Steps for testing gas piping for leaks and pressure.

Testing Gas Supply Pressure

How to test and verify gas supply pressure.

System Service Checks - Gas Flow and Burners

Proper Gas Flow Check

How to check for proper gas flow to burners.

Inshot Burner Service

Details the inshot burner assembly and its servicing.

Spark Electrode Gap Adjustment

Explains how to check and set the spark electrode gap.

Heat Exchanger Access

Procedures for accessing and removing the heat exchanger.

Component Maintenance and Checks

Evaporator Coil Inspection and Cleaning

Instructions for inspecting and cleaning the evaporator coil.

Condenser Coil Cleaning

Procedures for cleaning condenser coils.

Electrical System Checks

Steps for checking electrical connections, voltage, and motors.

Accessories Information

Mounting Frames

Information on roof mounting frames for unit installation.

LP Propane Kit

Details the LP/propane conversion kit.

Dirty Filter Switch S27

Explains the function of the dirty filter switch.

Transitions

Describes optional supply/return transitions.

Air Management and Blower Components

Outdoor Air Dampers

Information on motorized and manual outdoor air dampers.

Supply and Return Diffusers

Details optional supply and return diffusers.

Blower Proving Switch S52

Explains the function of the blower proving switch.

Economizer Operation and Controls

Economizer Installation

Notes economizer can be field or factory installed.

Free Cooling Modes

Describes the free cooling modes available.

Unit Controller Settings for Economizer

How to adjust economizer settings via the Unit Controller.

Exhaust Dampers and Fans

Gravity Exhaust Dampers

Explains the use of gravity exhaust dampers.

LAPEF Power Exhaust Fans

Details the use of LAPEF power exhaust fans.

Optional Kits and System Controls

Optional Cold Weather Kit (Canada)

Details the optional cold weather kit for Canada.

Control Systems Overview

Overview of the A55 Unit Controller and its capabilities.

Indoor Air Quality (CO2) Sensor A63

Explains the CO2 sensor and its effect on economizer operation.

Drain Pan Overflow Switch S149 (Optional)

Describes the drain pan overflow switch and its function.

Factory Installed Hot Gas Reheat Option

General Description

Provides a general description of hot gas reheat operation.

Reheat Mode Refrigerant Routing

Shows the refrigerant flow during reheat mode.

Cooling Mode Refrigerant Routing

Shows the refrigerant flow during cooling mode.

Reheat Coil Solenoid Valve and Setpoints

L14 Reheat Coil Solenoid Valve Operation

Explains the operation of the reheat coil solenoid valve.

Reheat Setpoint Adjustment

How to adjust the reheat setpoint.

Reheat Operation Check-Out

Procedure for testing hot gas reheat operation.

Default Reheat Operation Modes

Table showing default reheat operation modes.

Belt Drive Supply Air Inverter Operation

Inverter Operation Sequence

Steps for operating the belt drive supply air inverter.

Supply Air Blower Staging Inputs

Diagram showing inputs for staging the supply air blower.

CFM Adjustment Procedures

Design Specifications Entry

How to enter design specified CFM into the controller.

Set Maximum CFM

How to set the maximum CFM for the blower.

Enter Design Specifications

Menu path to enter design specified CFM.

Set Damper Minimum Position

How to set minimum damper positions for ventilation.

Direct Drive Supply Air Inverter Configuration

Set Blower Speed

How to set blower speed for direct drive systems.

Set Damper Minimum Position

How to set minimum damper positions for ventilation.

Staged Supply Air Operation Modes

Two-Stage Thermostat Operation

Describes two-stage thermostat operation with economizer.

Three-Stage Thermostat or Zone Sensor Operation

Describes three-stage thermostat operation.

Wiring Diagram - Constant Supply Air, Belt Drive

LGH092102120 H Constant Supply Air

Wiring diagram for constant supply air, belt drive blower units.

Wiring Diagram - LGH150 H Constant Supply Air

LGH150 H - Y Constant Supply Air

Wiring diagram for LGH150H constant supply air, belt drive blower units.

Wiring Diagram - LGH150 H G, J, M Constant Supply Air

LGH150 H G, J, M Constant Supply Air

Wiring diagram for LGH150H G, J, M constant supply air, belt drive blower.

Sequence of Operation - LGH092150

Power Sequence

Describes the power sequence for unit operation.

Blower Operation Sequence

Details the blower operation sequence.

Economizer Operation Sequence

Explains the economizer operation sequence.

1 st Stage Cooling Sequence

Sequence for first stage cooling.

Wiring Diagram - Staged Supply Air, No Bypass

LGH092152 U Staged Supply Air, No Bypass

Wiring diagram for staged supply air, no bypass, belt drive blower units.

Sequence of Operation - M3 Units

Power Sequence for M3 Units

Describes the power sequence for M3 units.

Blower Operation Sequence for M3 Units

Details blower operation for M3 units.

Economizer Operation for M3 Units

Explains economizer operation for M3 units.

1 st Stage Cooling Sequence for M3 Units

Sequence for first stage cooling on M3 units.

Gas Heat Sequence of Operation (LGH092150)

First Stage Heat Sequence

Describes the first stage heating sequence.

Second Stage Heat Sequence

Details the second stage heating sequence.

End of Second Stage Heat

Indicates when second stage heat ends.

End of First Stage Heat

Indicates when first stage heat ends.

Gas Heat Sequence of Operation (LGH092150) - Continued

Optional Low Ambient Kit Sequence

Explains the low ambient kit sequence.

Thermostat Connections

Electronic or Electromechanical Thermostat

Diagram showing thermostat connection points.

Economizer Operation and Settings

Economizer Power Sequence

Describes the power sequence for the economizer.

Economizer Operation

Explains how the economizer operates with the unit controller.

Wiring Diagram - Staged Supply Air, No Bypass

LGH092102120 H Staged Supply Air, No Bypass

Wiring diagram for staged supply air, no bypass, belt drive blower units.

Wiring Diagram - Staged Supply Air, No Bypass (LGH150 H)

LGH150 H - Y Staged Supply Air, No Bypass

Wiring diagram for LGH150H staged supply air, no bypass, belt drive blower.

Wiring Diagram - Staged Supply Air, No Bypass (LGH150 H G, J, M)

LGH150 H G, J, M Staged Supply Air, No Bypass

Wiring diagram for LGH150H G, J, M staged supply air, no bypass, belt drive blower.

Wiring Diagram - Staged Supply Air, With Bypass

LGH092102120 H Staged Supply Air, With Bypass

Wiring diagram for staged supply air, with bypass, belt drive blower units.

Wiring Diagram - Staged Supply Air, With Bypass (LGH150 H)

LGH150 H - Y Staged Supply Air, With Bypass

Wiring diagram for LGH150H staged supply air, with bypass, belt drive blower.

Wiring Diagram - Staged Supply Air, With Bypass (LGH150 H G, J, M)

LGH150 H G, J, M Staged Supply Air, With Bypass

Wiring diagram for LGH150H G, J, M staged supply air, with bypass, belt drive blower.

Wiring Diagram - Staged Supply Air, With Bypass (LGH092-152 U)

LGH092-152 U Staged Supply Air, With Bypass

Wiring diagram for LGH092-152U staged supply air, with bypass, belt drive blower.

Supply Air Inverter Sequence of Operation

No Bypass Sequence of Operation

Sequence of operation for supply air inverter without bypass.

Factory-Installed Bypass Sequence of Operation

Sequence of operation with factory-installed bypass.

A96 Inverter Fault Sequence

Fault sequence for the A96 inverter.

Blower Fault Sequence (No S52)

Troubleshooting sequence for direct drive blower without S52.

Direct Drive Blower Operation and Troubleshooting

Direct Drive Blower Operation

Describes the operation of the direct drive blower.

Blower Fault Sequence (No S52)

Fault sequence for direct drive blower without S52.

Blower Fault Sequence (With S52)

Fault sequence for direct drive blower with S52 configured.

Direct Drive Blower Troubleshooting

Failure Handling and Troubleshooting Steps

Steps for troubleshooting blower failures and alarms.