Page 77
B-Fin/Tube Coil
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no fur-
ther adjustment. If the system requires additional refrig-
erant,reclaim the charge, evacuate the system and add
required nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C), the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in normal cooling mode.
1 - Attach gauge manifolds and operate unit in cooling
mode with economizer disabled until system
all outdoor air dampers are closed.
2 - Check each system separately with all stages
operating.
3 - Use a thermometer to accurately measure the
outdoor ambient temperature.
4 - Apply the outdoor temperature to tables 24 through
35 to determine normal operating pressures.
Pressures are listed for sea level applications at
5 - Compare the normal operating pressures to
the pressures obtained from the gauges. Minor
variations in these pressures may be expected due
could mean that the system is not properly charged
or that a problem exists with some component in
the system. Correct any system problems before
proceeding.
6 - If discharge pressure is high, remove refrigerant
from the system. If discharge pressure is low, add
refrigerant to the system.
• Add or remove charge in increments.
• Allow the system to stabilize each time refrigerant
is added or removed.
7 - Use the following approach method along with the
TABLE 24
LG/LC Series 156H Std.
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
255 136 263 136 273 140
301 311 144
333 141 342 141 353 146
378 144 387 143 148
431 148 438 145 150
484 150 146 502 152
TABLE 25
LG/LC Series 156H Reheat
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
265 134 273 135 273 140
302 138 311 138 311 144
343 140 352 140 353 146
388 143 142 148
441 147 448 144 150
500 145 502 152
TABLE 26
LG/LC Series 180H Std.
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
248 137 257 135 137
285 137 137
328 143 336 338 140
374 146 383 141 385 144
425 148 433 144 435 147
151 488 147 488 151
TABLE 27
LG/LC Series 180H Reheat
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
258 136 267 133 137
138 304 135 137
338 142 346 137 338 140
384 145 385 144
435 147 443 142 435 147
488 150 145 488 151
TABLE 28
LG/LC Series 180U
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2
Dis. +10
psig
Suc. +5
psig
Dis. +10
psig
Suc. +5
psig
258 136 267 133
138 304 135
338 142 346 137
384 145
435 147 443 142
488 150 145