TABLE 29 - LG/LCSeries 210H Std.
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc. +5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 246 138 252 142 264 138
 284 142  145 306 140
 326 145 335 147 348 142
 373 148 380   144
 422 150 430 151 441 145
 472 153 482 154  148
TABLE 30 - LG/LC Series 210H Reheat
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2 Circuit 3
Dis.
+10
psig
Suc. +5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 258 136 264 141 264 138
  140 306 144 306 140
 338 143 347 146 348 142
 385 146  148  144
 434 148 442 150 441 145
 484 151  153  148
TABLE 31 - LG/LC Series 240H Std
Outdoor
Coil
Enter-
ing Air
Temp
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 255 137 246 132 260 141 252 135
  140 284 137  144  137
 332 142 325 140 340 146 331 
 378 145 371 142 385 148 377 141
 428 148 421 145 436 150 428 143
 481 151 473 148 488 153  145
TABLE 32 - LG/LC Series 240H Reheat
Outdoor
Coil
Enter-
ing Air
Temp
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 255 137 246 132 260 141 252 135
  140 284 137  144  137
 332 142 325 140 340 146 331 
 378 145 371 142 385 148 377 141
 428 148 421 145 436 150 428 143
 481 151 473 148 488 153  145
TABLE 33
LG/LC Series 240U
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2
Dis. +10
psig
Suc. +5
psig
Dis. +10
psig
Suc. +5
psig
 251 127 262 128
  132 303 133
 331 135 347 136
 376 137  
 426 141 443 142
  144  145
TABLE 34 - LG/LC Series 300S Std.
Outdoor
Coil
Enter-
ing Air
Temp
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 272  273 128 280  277 127
 311 132 303 131 321 131 317 
 357 134  133 367 133 363 130
 403 137  137 418 135 406 134
 451  453 140 475 138 471 136
 502 142 505 142 532 144  140
TABLE 35 - LG/LC Series 300S Reheat
Outdoor
Coil
Enter-
ing Air
Temp
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
Dis.
+10
psig
Suc.
+5
psig
 272  273 128 280  277 127
 311 132 303 131 321 131 317 
 357 134  133 367 133 363 130
 403 137  137 418 135 406 134
 451  453 140 475 138 471 136
 502 142 505 142 532 144  140
TABLE 36
LG/LC Series 300U - 580965-01
Outdoor
Coil En-
tering Air
Temp
Circuit 1 Circuit 2
Dis. +10
psig
Suc. +5
psig
Dis. +10
psig
Suc. +5
psig
 268  265 113
 313 128  120
 358 135 351 126
  140 405 131
 470 143 463 136
 532 151 505 127