EasyManua.ls Logo

Lennox LGH240H

Lennox LGH240H
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...

C-Zone Sensor (4 Clg. Stages), 4-Compressor Units
1-Economizer With Outdoor Air Suitable Y1 Demand -
󰀨
Blower Cooling Low
Dampers modulate
Y2 Demand -
󰀨
Blower Cooling High
Dampers Modulate
156, 180H, 210, 240H, 300S - If dampers are at maximum
open for three minutes, compressor 1 is energized and
blower stays on cooling high.
180U, 240U, 300U - If dampers are at maximum open for
three minutes, two compressors (one from each circuit)
are energized and blower stays on cooling high.
Y3 Demand -
Compressors 1 and 2 On
180U, 240U, 300U - Two Compressors On
(one from each circuit)
Blower Cooling High
Dampers Maximum Open
Y4 Demand -
All Compressors On
Blower Cooling High
Dampers Maximum Open
2-No Economizer or Outdoor Air Not Suitable
Y1 Demand -
Compressor 1 On
180U, 240U, 300U - Two Compressors On
(one from each circuit)
Blower Cooling Low
Y2 Demand -
Compressors 1 and 2 On
180U, 240U, 300U - Two Compressors On
(one from each circuit)
Blower Cooling Medium Low
Y3 Demand -
Compressors 1, 2 and 3 On
180U, 240U, 300U, any three compressors are On
Blower Cooling Medium High
Y4 Demand -
All Compressors On
Blower Cooling High
X--VAV System
Refer to the installation instructions for additional informa-
tion and available replacements.
Units may contain an optional supply air blower equipped
       
supply air CFM.
-

NOTE - Units equipped a Variable Frequency Drive (VFD)
are designed to operate on balanced, three-phase power.
Operating units on unbalanced three-phase power will re-
duce the reliability of all electrical components in the unit.
Unbalanced power is a result of the power delivery system
supplied by the local utility company. Factory-installed in-
verters are sized to drive blower motors with an equiva-
lent current rating using balanced three-phase power. If
unbalanced three-phase power is supplied; the installer
must replace the existing factory-installed inverter with an
inverter that has a higher current rating to allow for the
imbalance.
A-Start-Up
1 - A pressure transducer (A30) is shipped in a box
in the blower compartment. Install the transducer
according to manufacturer's instructions.
Note - Make sure the transducer is installed in the
main duct at least 2/3 of the distance away from the
unit.
2 - Two twisted pairs of shielded cable must be used to

P300 connector is hanging in the control box.
3 - Open all zone dampers and/or boxes.
4 - 
5 - Use the Unit Controller to calibrate the blower CFM.
Select the SETUP->TEST & BALANCE->BLOWER
menu to start the blower. The Unit Controller
will display the percent of blower speed. Adjust
      

6 - Press SAVE to display the current static pressure. If

press SAVE again to set the setpoint. If the static
      
adjust the pressure and press SAVE to set the
setpoint.
7 - Record new setpoints in table 43.
PRESSURE TRANSDUCER WIRING
TWISTED
PAIR
UNUSED WIRE
DRAIN
NOT
CONNECTED
NOT
CONNECTED
TWISTED
PAIR
A30
+S
_
+
J300
1
2
3
FIGURE 40

Other manuals for Lennox LGH240H

Related product manuals