GAS HEAT SEQUENCE OF OPERATION LGT092H-150H
First Stage Heat:
1 - 
2 - 
A3 Ignition Control. The Ignition control then routes
        
Ignition control energizes the combustion air blower
B6.
3 - After the combustion air blower B6 has reached
       
contacts close. The A3 routes 24VAC through N.C.
       
contacts of combustion air proving switch S18 to
energize the ignition module A3.
4 -         

Second Stage Heat:
 
demand initiates W2 in the thermostat.
6 - 
Unit Controller.
 

valve GV1.
End of Second Stage Heat:
8 - 
is de-energized.
9 -      
module.
End of First Stage Heat:

is de-energized.
11 - 
turn de-energizing terminal LO of GV1. Combustion
air blower relay K13 located in the A3 ignition control
is also de-energized.
Optional Low Ambient Kit:

12 - 
only) is routed through the low ambient kit fuses

