EasyManua.ls Logo

Lennox M33C024S4

Lennox M33C024S4
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
95
24.2.2. Pressure (PSI)
580
507
43
5
3
62
290
217
55
65
75
Outdoor
t
57F (13.89) 47F (8.33) 37F (2.78) 27F 17F
(-2.78) (-8.33)
24.3. Capacity Request Calculations
Total capacity Request=Σ(Norm code × HP) /10× modify rate+ correction.
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Figure 38. Cooling Mode
Capacity Area a b c d e f
Norm Code (N) 3 2 1.5 1 .5 0
Model 9K 12K 18K
HP 1.0 1.2 1.5
NOTE: The nal result is integer.
Plus all the indoor capacity request together, then modify it by T4.
When there is only one indoor unit:
Outdoor Temperature (T4)
Cooling
>29°C 18°C to 29°C <17°C
>84.2°F 64.4°F to 84.2°F <62.6°F
Modify Rate 100% 60% 40%

Table of Contents

Related product manuals