Page 8
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
NOTE-The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per hour
of the total input rating of all equipment in the enclosure.
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12” above
bottom)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
FIGURE 8
EQUIPMENT IN CONFINED SPACE -
ALL AIR FROM OUTSIDE
OUTLET AIR
INLET AIR
NOTE-Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm
2
per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
FIGURE 9
Shipping Bolt Removal
Units with 1/3HP and 1/2HP blower motors are equipped
with three exible legs and one shipping leg. See gure
10. In some units with 1/3HP blower motor, the shipping
leg is exible with rubber mounting grommets similar to
the other three mounting legs and require no modication.
The rest of the units with 1/3HP and 1/2HP blower motors
(these blower motor housings will be tagged) have a rigid
shipping leg equipped with a shipping bolt and at white
plastic washer. The bolt and washer must be removed
before the furnace is placed into operation. After the
bolt and washer have been removed, the rigid leg will not
touch the blower housing.
RIGID LEG
(Remove shipping bolt
and washer)
Blower motor with three exible legs and one
rigid shipping leg. Blower motor housings
will be tagged for shipping bolt removal
FIGURE 10
Installation - Setting Equipment
WARNING
Do not connect the return air duct to the back of the
furnace. Doing so will adversely affect the operation of
the safety control devices, which could result in personal
injury or death.
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Upow Applications
The ML193UH gas furnace can be installed as shipped
in the upow position. Refer FIGURE 12 for clearances.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit front].
The unit must be level from side to side. Unit may be posi-
tioned from level to 1/2” toward the front to aid in draining.
See FIGURE 11.
Allow for clearances to combustible materials as indicated
in the unit nameplate.