Page 46
Testing  for  Proper  Venting  and  Sucient 
Combustion Air for Non-Direct Vent Applications
 WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each 
appliance connected to the venting system being placed 
into operation could result in carbon monoxide poisoning 
or death. The following steps shall be followed for each 
appliance connected to the venting system being placed 
into operation, while all other appliances connected to 
the venting system are not in operation.
After the ML196UHE gas furnace has been started, the 
following test should be conducted to ensure proper vent-
ing and sucient combustion air has been provided to the 
ML196UHE as well as to other gas-red appliances which 
are separately vented.
If a ML196UHE furnace replaces a Category I furnace 
which was commonly vented with another gas appliance, 
the  size  of  the  existing  vent  pipe  for  that  gas  appliance 
must be checked. Without the heat of the original furnace 
ue products, the existing vent pipe is probably oversized 
for the single water heater or other appliance. The vent 
should be checked for proper draw with the remaining ap-
pliance.
The test should be conducted while all appliances (both 
in operation and those not in operation) are connected to 
the venting system being tested. If the venting system has 
been installed improperly, or if provisions have not been 
made for sucient amounts of combustion air, corrections 
must be made as outlined in the previous section.
1 -   Seal any unused openings in the venting system.
2 -  Visually inspect the venting system for proper size and 
horizontal pitch.  Determine there is  no blockage  or 
restriction, leakage, corrosion, or other deciencies 
which could cause an unsafe condition.
3 -  To the extent that it is practical, close all building 
doors and windows and all doors between the space 
in which the appliances connected to the venting 
system are located and other spaces of the building.
4 - Close replace dampers.
5 -  Turn on clothes dryers and any appliances not 
connected to the venting system. Turn on any 
exhaus fans, such as range hoods and bathroom 
exhausts, so they will operate at maximum speed. 
Do not operate a summer exhaust fan.
6 -  Follow the lighting instruction to place the appliance 
being inspected into operation. Adjust thermostat so 
appliance will operate continuously.
7 -  Use the ame of match or candle to test for spillage 
of ue gases at the draft hood relief opening after 5 
minutes of main burner operation.
8 -   If improper venting is observed during any of the 
above tests, the venting system must be corrected 
or  sucient  combustion/make-up  air  must  be 
provided.  The  venting  system  should  be  re-sized 
to  approach  the  minimum  size  as  determined  by 
using the appropriate tables in appendix G in the 
current standards of the National Fuel Gas Code 
ANSI-Z223.1/NPFA 54 in the U.S.A., and the 
appropriate Natural Gas and Propane appliances 
venting  sizing  tables  in  the  current  standard  of  the 
CSA-B149 Natural Gas and Propane Installation 
Codes in Canada.
9 -  After determining that each appliance remaining 
connected to the common venting system properly  
events when tested as indicated in step 3, return 
doors,  windows,  exhaust  fans,  replace  dampers 
and any other gas-burning appliance to their previous 
condition of use.
Other Unit Adjustments
Primary Limit.
The primary limit is located on the heating compartment 
vestibule panel. This limit is factory set and requires no 
adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located in the burner 
box.
Pressure Switch
The pressure switch is located in the heating compartment 
on the cold end header box. This switch checks for proper 
combustion air inducer operation before allowing ignition 
trial. The switch is factory-set and must not be adjusted.
Temperature Rise
After the furnace has been started and supply and return 
air temperatures have been allowed to stabilize, check the 
temperature rise. If necessary, adjust the blower speed to 
maintain the temperature rise within the range shown on 
the unit nameplate. TABLE 18 on page 56 allowable 
heating speeds. Increase the blower speed to decrease 
the temperature. Decrease the blower speed to increase 
the temperature rise. Failure to adjust the temperature 
rise may cause erratic limit operation.
Fan Control
Fan On Delay
The heat fan on time of 30 seconds is not adjustable. The 
cool fan on delay is 2 seconds and not adjustable.
Fan O Delay
The  heat  fan  o  delay  (amount  of  time  that  the  blower 
operates after the heat demand has been satised) may 
be adjusted by changing the jumper position across the 
ve pins on the integrated control. The unit is shipped with 
a factory fan o setting of 90 seconds. The fan o delay 
aects comfort and is adjustable to satisfy individual ap-
plications. Adjust the fan o delay to achieve a supply air 
temperature between 90° and 110°F at the moment that 
the blower is de-energized. Longer o delay settings pro-
vide lower return air temperatures; shorter settings pro-
vide higher return air temperatures. See Figure 62. The 
cool fan o delay (amount of time that the blower operates
after the cool demand has been satised) is 45 seconds 
and not adjustable.