EasyManua.ls Logo

Lennox MLA009S4S-1P - Page 139

Lennox MLA009S4S-1P
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
139
Error Code: F3
Description: Compressordischargetemperaturesensorerror
General Note: Whenthecompressordischargetemperature(T5)ismorethan115°Cfor10seconds,thecompressorwillstopandrestart
tillT5islessthan90°C.
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan115°C?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringcon-
nection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Other manuals for Lennox MLA009S4S-1P

Related product manuals