EasyManua.ls Logo

Lennox MPA036S4M-1P - E4 Fault Code

Lennox MPA036S4M-1P
258 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lennox Mini-Split Service Manual / Page 204
E4 Fault Code
Basic Description:
Indoor return air temperature sensor error.
General Note:
If the voltage is lower than 0.06V or higher than 4.94V, the LED will display the error.

Table of Contents

Related product manuals