Page 38
Burner runs continuously cont.
Source Procedure Causes Correction
Too much combustion air Reduce combustion air.
Air leaks into heat exchanger
around inspection door, etc.
Correct cause of air leak.
ow
2
ess
than 10%.
Excessive draft
Adjust barometric draft con
trol for correct draft.
Incorrect burner head adjust
ment
Correct burner head setting.
Dirty or plugged heat exchanger
Clean heat exchanger.
r
y or p
ugge
ea
exc
anger
Readjust burner.
High smoke
readin
more
Insufficient draft Increase draft.
Combustion
ec
urner
combustion for
CO2, stack tem
than a trace. Incorrect burner head adjust
ment
Correct burner setting.
perature, and
Too little combustion air Increase combustion air.
smo
e
Too little blower air
Increase blower speed to
maintain proper temp. rise.
Hi
h stack tem
Blower belt too loose (if
equipped)
Tighten blower belt.
perature is
Dirty or plugged heat exchanger Clean heat exchanger.
more t
an
550
F Net.
Dirty blower wheel Clean blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or
dampers
Readjust registers or damp
ers.
Inspect fire and check
Partially plugged or defective
nozzle
Replace nozzle.
ressure
oil pressure.
Oil pressure is too low: less
than 100 psi.
Increase oil pressure top
100psi.
Troubelshooting O23 / OHR23 / OF23 −5 Units
Procedure Status Correction
CONDITION 1: BURNER DOES NOT ENERGIZE WITH A CALL FOR HEAT.
1.1 Check limit switch contacts are
closed and clean.
Clean contacts. Replace limit switch if necessary.
1.2 Check for line votage at oil pri
mary control. Voltage should be
120V
Check primary voltage source. Take appropiate measures to cor
rect if necessary.
1.3 Check LED light with burner off,
no call for heat (no flame)
LED is on
Cad cell or control is bad. Control sees external light or connections
are shorted. See step 1.4.
no ca
or
eat
no
ame
LED is off See step 1.5.
LED is off Eliminate exteranl light or shield light from cad cell
1.4 Sheild cad cell from external
light
LED stays on
Replace cad cell and recheck.
If LED stays on remove cad cell lead wires from burner control
and recheck.
If LED turns off, replace cad cell bracket assembly.
If LED stays on replace buner control
1.5 On warm air systems, Remove
one thermostat lead and jumper
Burner energizes
Trouble in thermostat or limit circuit. Check thermostat or limit wir
ing connections.
one t
ermostat
ea
an
umper
thermostat (T to T) terminals on
burner control.
Burner does not energize
Disconnect line voltage power and open line switch
Check all wiring and tighten any loose connections. Recheck
If burner does not energize replace burner control