Menu Interface SERVICE
From the DISPLAY mode, press and then use to
scroll to SERVICE. Next, press
to enter the SERVICE
menu. Use until desired item is displayed.
SERVICE
TEST
OFFLINE
IN / OUTPUTS
REPLACE
REPORT
Use arrows to move
Using SERVICE, you may run tests that
check a functional operation (e.g. HEAT-
ING) or you may run tests that single out
a system component for checking. The
diagram below shows how to navigate
through the system to access a functional
test or a component test.
When the list of tests appears, use the
up/down arrows until the test you want to
run appears. Then press the SELECT
BUTTON to begin running the test.
SERVICE > TEST
In the SERVICE menu, use until TEST is displayed.
Press to enter the TEST menu.
Use arrows to move
GUIDED
BLOWER
FANS
COOL
HEAT
DAMPER
REHEAT
SENSORS
OUTPUTS
CONTROLLER
TEST
TEST is described in
detail in table 4
[Page 8]).
Using the TEST menu, the service technician may run a
sequence of tests to gather information available while that
component is turned on. The unit will return to normal
mode when leaving the TEST menu. See table 4 for de-
tails.
Any Status/Alarm codes found during testing will be logged
to the event history.
Upon exit from TEST mode, the unit will return to normal
operation if no key is pushed for 1 hour.
SERVICE > OFFLINE
In the SERVICE menu, use until OFFLINE is dis-
played. Press to enter the OFFLINE menu.
Use arrows to move
LOCKOUT
BLOWER ONLY
COOLING ONLY
HEATING ONLY
RESET
OFFLINE
SERVICE > IN / OUTPUTS
In the SERVICE menu, use until IN / OUTPUTS is dis-
played. Press to enter the IN / OUTPUTS menu.
Use arrows to move
ZONING
SENSORS
RELAYS
NETWORK
OUTPUTS
IN/OUTPUTS
SERVICE > REPLACE
In the SERVICE menu, use REPLACE to reset the runtime
counters for the listed device when a new hardware com-
ponent has been installed in the system.
Use until REPLACE is displayed. Press to enter
the REPLACE menu. This will reset the runtime for the new
part to zero.
Use arrows to move
FILTER
BELT
UV LAMP
FANS
BLOWER
COMPRESSOR
REPLACE