Page 42 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
Min. Factory Maxi.
27 (FLEXY™ only)
Mode, Fan low speed, dead zone Off # On
28 (FLEXY™ only)
Mode, Fan low speed automation Off # On
29 (on = unit runs at maximum 50% during "night mode")
Mode, Low noise Off # On
30 (J-BUS only)
Remote control, overide, Mode Off Off On
31 (J-BUS only)
Remote control, Overide, Low fan speed Off Off On
32 (J-BUS only)
Remote control, Overide damper with recycled air Off Off On
33 (J-BUS only)
Remote control, Overide damper with minimum fresh air Off Off On
34 (J-BUS only)
Remote control, Overide damper with fresh air Off Off On
35 (J-BUS only)
Remote control, Overide 50% load limit Off Off On
36 (J-BUS only)
Remote control, Overide heating cancellation Off Off On
37 (J-BUS only)
Remote control, Overide cooling cancellation Off Off On
38 (J-BUS only)
Remote control, Overide electrical heaters cancellation Off Off On
39 On = Electrical heaters during defrosting Off On On
40 (Alarm only)
Room temperature, low setpoint 5.0 10.0 20.0
41 (Alarm only)
Room temperature, high setpoint 20.0 40.0 40.0
42 Room relative humidity (%), low setpoint 0 0 50
43 Room relative humidity (%), high setpoint 50 100 100
44 Room absolute humidity (g/kg), low setpoint 0.0 0.0 30.0
45 Room absolute humidity (g/kg), high setpoint 0.0 30.0 30.0
46 Temperature, Curved gradient of anticipated speed 0.0 10.0 20.0
47 (0 = Start at times set in "modes" only, no anticipation start 0 12 100
Value, Gradient of anticipated speed
48 Quantity of CO2, Ppm, minimum fresh air 0 1000 2000
49 Quantity of CO2, Ppm, maximum fresh air 0 1500 2000
50 Percentage, Fresh air damper opening before fan will start 0 10 100
2nd Level
Min. Factory Maxi.
51 Maximum temperature, required setpoint for room, day mode 21.0 27.0 35.0
52 Minimum temperature, required setpoint for room, day mode 8.0 17.0 21.0
53 (Compressor minimum run time in seconds) 25 180 1800
54 Differential temperature, engaged heat setting 0.0 1.0 10.0