Page 44 - IOM / ROOF-TOP FLEXY™ Series
USING THE KP02 MAINTENANCE CONTROL DISPLAY
Min. Factory Maxi.
87 Coefficient, icing time, condenser coil 0 3 12
88 Number, condenser restart, condenser coil 1 1 8
89 Low temperature, setpoint,
air/water cooled heat exchanger (non standard) 4.0 5.0 20.0
90 High temperature, setpoint,
air/water cooled heat exchanger (non standard) 20.0 45.0 46.0
91 Outside temperature, setpoint, 100% electrical heater discharge
(Outdoor air > Setpoint 91 = electric heater stop) -20.0 10.0 30.0
92 Sensing setpoint, air flow cutout 0.0 0.2 5.0
93 Sensing setpoint, clogged filters 0.0 2.5 5.0
94 Sensing setpoint, missing filters 0.0 0.5 5.0
95 KP17 = on = On/Off unit Off Off On
96 Delay, closing, KP 12-2 "Day" input 4 60 65535
97 Delay, Opening, KP 12-2 "Day" input 2 300 65535
98 Unit type 0 0 65535
99 On = "LINEA™"* series, Off = "FLEXY™" series Off # On
100 On = Low ambiant Option fitted
(Disable setpoints 79 & 80) (Off = Enable setpoints 79 & 80) Off # On
101
(FLEXY™ only)
On = Advanced Control Pack option fitted Off # On
102 Slave J-Bus, number 1 1 10
103 Link, number 0 0 7
104 All setpoint values overide to factory
default EPROM values (centre column) Off Off On
105 Test stages (for factory test procedures only
reduces all delay timers to 0) 0 0 65535
* : LINEA is another range of LENNOX ROOFTOP. For more information, please consult your regional office