THERMOSTAT INSTALLER SETUP OPTIONS
Factory setting
Other choices
(press
▲
or
▼
key to change)
Actual
setting
Select
Installer setup
number (press
unocuppied
temp. key to
change
Display Description Display Description
Not used 1 - - - - -
Fan operation
a
20
Conventional applications
where equipment controls
fan operation in heat
mode
1
Electric heat applications where
thermostat controls fan
operation in heat mode.
Output stages of
heating
3
Depends
on
subbase
Stages of heat
0, 1, 2, or
3
0 -No heating
1 -One stage of heat
2 -Two stages fo heat
3 -Three stages of heat
Output stages of
cooling
8
Depends
on
subbase
Stages of cooling
0, 1, 2 or
3
0 – No cooling
1 – One stage of cool
2 – Two stages of cool
3 – Three stages of cool
System setting
adjustment
(models with
system key)
12
Depends
on model
System selection 0, 1 or 2
0 – System setting key is
operational
1 – Auto setting is disabled
2 – Auto setting only
Not used 13 - - - - -
Degree
temperature
display
14 0
Temperature is displayed
in °F
1 Temperature is displayed in °C
Displaying
temperature
(T7300 F only)
15 0 Temperature is displayed 1 Temperature is not displayed
Clock format 16 0 12-hour clock format 1 24-hour clock format
Intelligent Fan™
operation
17 2
Fan operates con-
tinuously in Occupied
and recovery modes.
Fan operates with call
for heating or cooling in
Unoccupied mode.
0 or 1
0 - Fan only operates with calls
for heating or cooling in
occupied and Unoccupied
modes.
1 - Fan operates continuously
in Occupied mode. Fan
operates with calls for
heating or cooling in
Unoccupied mode
Auxiliary contact
operation
18 0 0 –Time of contact day 0 or 1 1 – Economiser contacts
Extended fan
operation in
heating
a
(T7300F only)
19 0
No extended fan
operation after the call for
heat ends
1
Fan operation os extended 90
seconds after the call for heat
ends.