E2016 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
General
This SL18XC1 outdoor air conditioner with all-aluminum
coil is designed for use with HFC-410A refrigerant only.
This unit must be installed with an approved indoor air han
dler or coil. See the Lennox SL18XC1 Product Specifica
tions bulletin (EHB) for approved indoor component match
ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
NOTICE !
For more in-depth information, consult the Installa
tion and Service Procedures manual, available as
Corp. 1405-L10 on DaveNet or through the Technical
Support department at 800-453-6669.
INSTALLATION
INSTRUCTIONS
Dave Lennox Signature
®
Collection SL18XC1 System
AIR CONDITIONERS
507353-01
7/2018
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju
ry or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch.
STEP 1 -- SETTING THE UNIT -- Clearances
CONTROL
PANEL ACCESS
LOCATION
6 (152)
36 (914)
12 (305)
30 (762)
24
(610)
LINE SET
CONNECTIONS
ACCESS PANEL
REAR VIEW OF UNIT
48 (1219)
MINIMUM CLEARANCE BETWEEN TWO UNITS
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
S Clearance to access panel must be 30
inches (762mm).
S Clearance to one of the other three
sides must be 36 inches (914mm).
S Clearance to one of the remaining two
sides may be 12 inches (305mm) and
the final side may be 6 inches
(152mm).
FIGURE 1
Question and Answer IconNeed help?

Do you have a question about the Lennox SL18XC1 and is the answer not in the manual?

Lennox SL18XC1 Specifications

General IconGeneral
SEER RatingUp to 18
RefrigerantR-410A
Energy Star CertifiedYes
StagesTwo-stage
Operating Voltage Range208/230V
Cooling Capacity (BTU/h)24, 000 - 60, 000
Compressor TypeTwo-Stage Scroll

Summary

STEP 2 -- ELECTRICAL -- Circuit Sizing and Wire Routing

OUTDOOR CONTROL (A175) JUMPERS AND TERMINALS

Configuration settings for compressor delay, defrost, and EDA applications.

FIELD CONTROL WIRING DIAGRAMS

Wiring illustrations for non-communicating and communicating thermostats.

STEP 3 -- REFRIGERANT PIPING -- Flushing Existing Line Set & Indoor Coil

STEP 4 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device

FLUSHING LINE SET PROCEDURE

Procedure for flushing the refrigerant line set.

STEP 5 -- REFRIGERANT PIPING -- Brazing Procedures

PREPARING LINE SET FOR BRAZING

Steps for removing panels, caps, and cores before brazing.

ATTACH MANIFOLD GAUGE SET

Connecting gauge set for brazing operations with nitrogen flow.

WRAP AND BRAZE SERVICE VALVES

Instructions on wrapping valves and brazing line sets with safety precautions.

STEP 6 -- INSTALLING INDOOR EXPANSION VALVE

STEP 7 -- LEAK TEST

STEP 8 -- EVACUATION