LIST OF SETPOINTS
1st Level
Min. Factory Maxi.
0 Password to access level 2 setpoints and variables 0 # 255
1 Temperature, required setpoint for room, day mode 8.0 21.0 35.0
2 (Used by KP17 only)
KP17 Remote control, overide, occupied mode Off Off On
3 (Used by KP17 only)
KP17 Remote control, overide, automatic mode Off Off On
4 (Used by KP17 only)
KP17 Remote control, overide, unoccupied mode Off Off On
5 Fault reset Off Off On
6 Remote control, On / Off, unit Off Off On
7
(Special software request)
Remote control, On / Off, customer output KP12/2
Off Off On
8 (Used for setting up different time zones) 0 0 7
Mode, Selection
0 = Day 1 = Week-end 2 = Night 3 =
4 = Morning 5 = Midday 6 = Evening 7 = BMS
9 Defines end of weekend/Start of week (1 = Sunday, 2 = Monday, etc) 1 # 7
Mode, day of the weekn start of mode
10 (Used with setpoint 8 - mode selection - to define the hour of the start time) 0 # 23
Mode, hour, start of mode
11 Used with setpoint 8 - mode selection - to define the minute of the start time 0 # 59
Mode, minute, start of mode
12 Defines end of week/Start of weekend (6 = Friday, 7 = Saturday, etc) 1 # 7
Mode,day of the week, end of mode
13 Used with setpoint 8 - mode selection - to define the hour of the stop time 0 # 23
Mode, hour, end of mode
14 Used with setpoint 8 - mode selection - to define the minute of the stop time 0 # 59
Mode, minute, end of mode
15 Defines day mode deadzone, other time zones = cooling setpoint) 8.0 # 35.0
Mode, temperture, room cooling setpoint
16 Defines day mode deadzone (other time zones = heating setpoint) 8.0 # 35.0
Mode, temperature, room heating setpoint
17 (FLEXY™ only)*
On = Absolute humidity (g/kg) / Off = Relative humidity (%) Off Off On
18 (FLEXY™ only)*
Mode, relative humidity (%), room minimum setpoint required 0 # 100
19 (FLEXY™ only)*
Room mode, Relative humidity (%), maximum setpoint required 0 # 100
20 (FLEXY™ only)*
Mode, Absolute humidity (g/kg), room minimum setpoint required 0.0 # 30.0
21 (FLEXY™ only)*
Mode, Absolute humidity (g/kg), room maximum setpoint required 0.0 # 30.0
22 Mode, Percentage, Minimum fresh air 0 # 100
23 Mode, Fan activity in control zone (cooling mode/heating mode) Off # On
24 Mode, Fan activity in dead zone Off # On
25 (Special application request only)
Mode, Fan automation, dead zone Off # On
26 (FLEXY™ only)*
Mode, Fan low speed, control zone Off # On