Page 74 - IOM / Rooftop Smart and Linéa™ Range
Min. Factory Maxi.
87 Coefficient, icing time, condenser coil 0 3 12
88 Number, condenser restart, condenser coil 1 1 8
89 Low temperature, setpoint,
air/water cooled heat exchanger (non standard) 4.0 5.0 20.0
90 High temperature, setpoint,
air/water cooled heat exchanger (non standard) 20.0 45.0 46.0
91 Outside temperature, setpoint, 100% electrical heater discharge
(Outdoor air > Setpoint 91 = electric heater stop) -20.0 10.0 30.0
92 Sensing setpoint, air flow cutout 0.0 0.2 5.0
93 Sensing setpoint, clogged filters 0.0 2.5 5.0
94 Sensing setpoint, missing filters 0.0 0.5 5.0
95 KP17 = on = On/Off unit Off Off On
96 Delay, closing, KP 12-2 "Day" input 4 60 65535
97 Delay, Opening, KP 12-2 "Day" input 2 300 65535
98 Unit type 0 0 65535
99 On = "LINEA™" series, Off = "FLEXY™" series* Off # On
100 On = Low ambiant Option fitted
(Disable setpoints 79&80) (Off = Enable setpoints 79 & 80) Off # On
101
(FLEXY™ only)*
On = Advanced Control Pack option fitted Off # On
102 Slave J-Bus, number 1 1 10
103 Link, number 0 0 7
104 All setpoint values overide to factory
default EPROM values (centre column) Off Off On
105 Test stages (for factory test procedures only
reduces all delay timers to 0) 0 0 65535
* : FLEXY™ is an other range of ROOFTOP. For more informations, please consult your regional office
USING THE KP02 MAINTENANCE CONTROL DISPLAUSING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLAUSING THE KP02 MAINTENANCE CONTROL DISPLA
USING THE KP02 MAINTENANCE CONTROL DISPLA
YY
YY
Y