BLOWER DATA
SLP98UH090V48C BLOWER PERFORMANCE (less lter)
RIGHT SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 764 828 956 1084 1213 1341 1469 1597
Increase (+7.5%) Heat CFM 705 766 888 1010 1132 1255 1377 1499
Default Heat CFM 645 703 819 936 1052 1168 1285 1401
Decrease (-7.5% ) Heat CFM 594 650 762 874 986 1099 1211 1323
Decrease (-15% ) Heat CFM 542 596 704 812 921 1029 1137 1245
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 840 955 1120 1280 1160 1360 1530 1740
Default Cool CFM 775 910 1010 1170 1060 1240 1400 1590
Decrease (-10%) Cool CFM 695 815 930 1045 925 1130 1295 1440
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 380 cfm (SLP98UH090V48C) and 450 cfm (SLP98UH090V60C).
SLP98UH090V60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 583 665 830 995 1159 1324 1488 1653
Increase (+7.5%) Heat CFM 540 618 774 930 1085 1241 1397 1553
Default Heat CFM 497 571 718 865 1012 1159 1306 1453
Decrease (-7.5% ) Heat CFM 439 507 644 781 917 1054 1191 1328
Decrease (-15% ) Heat CFM 380 443 570 697 823 950 1076 1203
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 1050 1270 1445 1620 1590 1815 2010 2195
Default Cool CFM 975 1120 1295 1460 1460 1645 1845 2010
Decrease (-10%) Cool CFM 865 1010 1120 1290 1320 1500 1645 1860