SLP98UHV / Page 24
BLOWER DATA
SLP98UH090XV36C BLOWER PERFORMANCE (less lter)
SINGLE SIDE RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 657 702 792 881 971 1061 1150 1240
Increase (+7.5%) Heat CFM 631 673 757 841 926 1010 1094 1178
Default Heat CFM 605 644 723 802 880 959 1037 1116
Decrease (-7.5% ) Heat CFM 574 608 676 745 814 882 951 1020
Decrease (-15% ) Heat CFM 542 571 630 689 747 806 864 923
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 610 705 795 920 840 1015 1165 1300
Default Cool CFM 560 640 715 810 770 910 1050 1190
Decrease (-10%) Cool CFM 525 605 665 725 695 795 945 1110
SLP98UH090XV36C BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 13 30 46 62 75 93 110 129 143 42 60 83 101 122 144 163 181 206 219 241
Medium-Low 25 45 62 80 96 115 134 151 173 78 104 122 144 170 195 215 239 265 283 308
Medium-High 36 55 79 95 117 139 156 178 199 133 154 175 213 236 269 282 309 336 357 381
High 62 83 105 128 148 163 193 210 234 210 229 259 291 317 344 366 391 415 441 466
Default Cool CFM
Low 9 28 38 55 71 83 100 116 135 28 48 65 86 104 124 142 164 182 199 219
Medium-Low 20 38 52 69 83 102 120 135 152 59 81 100 125 142 162 182 204 229 248 269
Medium-High 26 46 63 83 101 117 141 157 178 95 118 142 165 192 213 244 264 288 314 329
High 39 59 81 98 121 143 161 180 202 149 171 199 229 257 285 306 330 359 389 403
Decrease (-10%) Cool CFM
Low 8 23 35 52 66 80 95 108 121 21 41 56 71 91 110 126 144 164 179 197
Medium-Low 12 29 44 59 75 92 111 126 140 35 56 73 95 115 137 155 176 198 216 235
Medium-High 20 37 56 71 86 104 122 143 155 70 89 114 135 157 175 199 225 242 266 282
High 27 47 67 82 102 124 142 160 181 104 125 150 178 207 232 251 273 297 321 350
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.