32
Service & Setup Functions
Forced cooling and manual defrost are service functions that can be performed from the outdoor unit.
Forced Cooling
Press and hold SW 1 FORCE_COOL and hold for 5 seconds.
Forced Cooling will override and disable all controllers restricting end-user(s) operation, this is to include
centralized controllers as well for a period of 60 minutes.
Compressor frequency, fan speeds, and EXV positions will be elevated and will operate semi-indepen-
dently from refrigerant pressures and temperatures.
Cooling and heating capacity demands will not be observed during this period.
Indoor units are in the cooling mode and fans are ON.
Manual Defrost
Press and hold SW 2 CHECK and SW 1 FORCE_COOL and hold for 5 seconds.
Manual Defrost will override and disable all controllers restricting end-user(s) operation, this is to include
centralized controllers as well for a period of 10 minutes (unless .
Compressor frequency, fan speeds, and EXV positions will follow automatic defrost logic. See service
manual.
Indoor units are in heating mode and fans are OFF.