33
Service Menu
Level 1 Menu Level 2 Menu Description
1 Cancel LVM Emergency Stop
0 None
1 Cancel LVM Emergency stop
2 Test Operation
0 None
1 Forced Cooling Test
2 Forced Heating Test
3 Auto Priority
0 50F (factory default)
1 60F
2 70F
4
Compressor Lockout
Temperature
1
None (factory default) Use only if no
alternate heat is used.
2 7F
3 10F
4 15F
5 20F
6 30F
7 40F
8 35F
9 40F
10 45F
11 50F
12 55F
13 60F
14 65F
15 70F
16 75F
17 80F
5 Indoor Unit Temperature Unit
0 °F
1 °C
Access Service Menu
Press SW 2 CHECK and hold for 5 seconds.
Press SW 1 FORCE_COOL to cycle through the Level 1 menu items. Press SW 2 CHECK to select the
current Level 1 menu item.
Press SW 1 FORCE_COOL to cycle through the Level 2 menu items. Press SW 2 CHECK to select the
current Level 2 menu item and return to the Level 1 menu.