Page 18
505367M 04/08
NOTE − A complete unit wiring diagram is located inside the unit control box cover.
Figure 32. Typical Wiring Diagram
Start−Up and Charging Procedures
IMPORTANT
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to
prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose
connections.
3. After evacuation is complete, open the liquid line and
suction line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on
power to the indoor blower and close the outdoor unit
disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the
procedures listed under Testing and Charging System
on page 17.
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit’s service
ports as illustrated in figure 3.
low pressure gauge to suction line service port.
high pressure gauge to liquid line service port.
INDOOR COIL AIRFLOW CHECK
Check indoor coil airflow using the Delta−T (DT) process
as illustration in figure 33.
DETERMINING CHARGE METHOD
To determine the correct charging method, use the
illustration in figure 34.

Other manuals for Lennox XC14

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox XC14 and is the answer not in the manual?

Lennox XC14 Specifications

General IconGeneral
Compressor TypeSingle-Stage
RefrigerantR-410A
Energy Star CertifiedYes
Cooling Capacity (BTU/h)18, 000 to 60, 000
Cooling Capacity1.5 - 5 tons
EER RatingUp to 13.00
Warranty10-year limited warranty on compressor, 5-year limited warranty on parts
SEER RatingUp to 16.00
CompressorScroll

Related product manuals