34
XC25
UNIT TYPE: The next item displayed is the self discovery
unit type. AC = air conditioner and HP = heat pump. If the
unit type cannot be determined, three bars appear.
POWER-UP / RESET:
FIRMWARE VERSION: During initial power-up or reset, the
first item displayed is the outdoor control firmware version.
Example to the right shows firmware version 2.3.
7-SEGMENT POWER-UP DISPLAY STRING

OR
OR
UNIT CODE: The next item to be displayed is the self discov
ery unit code. (may be a single character or two characters).
If the unit code cannot be determined, three bars appear.

THROUGH
OR
(These are just examples of firmware version, unit type,
unit nominal capacity and unit codes.)
UNIT CODE
UNIT TYPE, SIZE AND MODEL
NOT PROGRAMMED
2-TON HEAT PUMP, XP25-024
3-TON HEAT PUMP, XP25-036
4-TON HEAT PUMP, XP25-048
5-TON HEAT PUMP, XP25-060
2-TON AIR CONDITIONER, XC25-024
3-TON AIR CONDITIONER, XC25-036
4-TON AIR CONDITIONER, XC25-048
5-TON AIR CONDITIONER, XC25-060
UNIT NOMINAL CAPACITY: The next item to be displayed
is the self-discovery unit nominal capacity. Valid capacities
are 24 for 2-ton, 36 for 3-ton, 48 for 4-ton and 60 for 5-ton
units. If the unit type cannot be determined, three bars ap
pear.

OR

7-SEGMENT POWER-UP DISPLAY STRING EXAMPLE
FIRMWARE
VERSION
UNIT
TYPE
UNIT
CAPACITY
UNIT
CODE
.
IDLE MODE
.
.
Figure 16. Outdoor Control 7-Segment Unit Status Displays
Table 7. Outdoor Control 7-Segment Unit Status Displays
Description Example of Display
Idle Mode: Decimal point flashes at 1 Hz.
Idle Mode: Decimal point flashes at 1 Hz (0.5 second on, 0.5 second off).
Display OFF.
Soft Disabled: Top and bottom horizontal line and decimal point
flash at 1 Hz.
Soft Disabled: Top and bottom horizontal line and decimal point flash at 1
Hz (0.5 second on, 0.5 second off). NOTE - Control should be replaced.
O.E.M. Test Mode
All segments flashing at 2 Hz (unless error is detected) NOTE - Control
should be replaced.
Anti-Short Cycle Delay
The middle line flashes at 1 Hz for 2 seconds, followed by a 2-second dis
play of the number of minutes left on the timer (value is rounded up: 2 min.
1 sec. is displayed as 3). If activated, the anti-short cycle delay time remain
ing is displayed (default is 300 sec./5 min.).
Cooling Cycle: Shows current percentage of maximum cooling
capacity. Example to the right indicates a cooling demand of 50
percent and a outdoor fan speed of 700 RPM.
The demand percentage is displayed first, followed by a pause, then the
outdoor fan speed and the ambient temperature.
pause pause