XP16
Table 1 − HFC−410A Normal Operating Pressures (Liquid +10 & Suction +5 psig) (XP16−XXX−230−04)
*Temperature
of the air
entering the
outdoor coil.
Model −024
−048 −060−
°F (°C)* Liquid Line Pressure/Vapor Line Pressure
Cooling
First Stage
(Low Capacity)
65 (18) 232 / 146 225 / 144 235 / 144 225 / 138
75 (24) 264 / 148 261 / 147 268 / 145 264 / 141
85 (29) 307 / 149 302 / 149 310 / 147 305 / 142
95 (35) 353 / 151 349 / 151 356 / 148 352 / 146
105 (41) 403 / 153 397 / 153 407 / 150 405 / 148
115 (45) 460 / 155 461 / 157 466 / 152 459 / 150
Cooling
Second Stage
(High
Capacity)
65 (18) 240 / 143 239 / 139 244 / 140 241 / 134
75 (24) 279 / 145 278 / 141 283 / 141 280 / 136
85 (29) 322 / 147 322 / 143 326 / 144 324 / 137
95 (35) 371 / 149 367 / 146 374 / 147 373 / 138
105 (41) 423 / 151 426 / 148 427 / 148 425 / 142
115 (45) 485 / 154 489 / 151 491 / 151 486 / 146
Heating
First Stage
(Low Capacity)
50 (10) 333 / 116 318 / 116 354 / 115 365/ 113
40 (4.5) 314 / 88 304 / 89 324 / 92 341 / 89
Heating
Second Stage
(High Capac-
ity)
50 (10) 346 / 109 333 / 110 370 / 110 369 / 107
40 (4.5) 321 / 89 314 / 88 345 / 92 348 / 86
30 (−1) 303 / 74 303 / 77 322 / 70 335 / 73
20 (−7) 286 / 59 289 / 63 305 / 61 318 / 59