4. Place your thumbs on the metal tabs of the fan-bracket-assembly levers and
pinch the tab and blue release latch together; then, raise the levers, raising the
fan-bracket assembly.
5. Grasp the levers and lift the fan-bracket assembly out of the server.
6. If you are instructed to return the fan-bracket assembly, follow all packaging
instructions, and use any packaging materials for shipping that are supplied to
you.
Installing the fan-bracket assembly
To install the fan-bracket assembly, complete the following steps.
1 Fan bracket 3 Fan-bracket latches
2 Lever 4 Lever
1. Align the guides on the left and right sides of the assembly with the slots in the
sides of the chassis.
2. Lower the fan-bracket assembly into the chassis.
3. Push the fan-bracket-assembly levers toward the rear of the server until they
stop; pinch the release latches and metal tabs together and push the levers
down into place.
4. Press down on the lever metal tabs and on the fans to make sure that the
fan-bracket assembly is fully seated.
5. Install the cover (see “Installing the cover” on page 57).
6. Slide the server into the rack.
7. Reconnect the external cables; then, reconnect the power cords and turn on the
peripheral devices and the server.
Attention: In a dc power environment, only trained service personnel other
than Lenovo service technicians are authorized to connect or disconnect power
to the dc power supply. See the documentation that comes with each dc power
supply.
Chapter 4. Removing and replacing server components 61