33 CMVPFB01A
Advanced Features
7 Advanced Features
7.1 Option Module Advanced Parameters
7.1.1 Module Revision
P401 - Module Revision
Default: 6.x.x Range: 6.0.0 - 6.9.9
Access: RO Type: Integer
Display reads 6.x.x where: 6 = PROFIBUS-DP Module and x.x = Module Revision
7.1.2 Module Status
P402 - Module Status
Default: N/A Range: 0 - 7
Access: RO Type: Integer
Table 30: Module Status
P402 Value Description
0 Not Initialised
1 Initialisation: Module to EPM
2 Initialisation: EPM to Module
3 Online
4 Error: Failed Initialisation
5 Error: Time Out
6 Error: Module Mismatch (P401)
7 Error: Protocol Mismatch (P400)
7.1.3 Restore Defaults
P403 - Restore Defaults
Default: N/A Range: 0 - 1
Access: RW Type: Integer
Table 31: Restore Defaults
P403 Value Description
0 No Action
1 Reset Module Parameters to Factory Defaults

Table of Contents