SMVector PROFIBUS-DP Communication Module
Communications Interface Reference Guide

Table of Contents

Questions and Answers

  • J
    jshepardJul 25, 2025
    How to troubleshoot no communication from Lenze AC Tech Control Unit option module?
    • H
      Howard MooreJul 26, 2025
      If the Lenze AC Tech Control Unit option module has no communications, it may be due to several reasons. First, the module might not be initialized: verify the drive to module connection and check parameters P400 and P402. Second, PROFIBUS-DP settings might be incorrect: check P410 and P411; if unsure, reset PROFIBUS-DP parameters to factory default using P403. Third, improper wiring could be the cause: check the wiring between the PROFIBUS-DP network and communication module, ensure the terminal block is properly seated, and check the connection between the module and the drive.
  • Z
    Zachary MullenAug 1, 2025
    Why does Lenze AC Tech Control Unit drive stop for no obvious reason?
    • J
      John SmithAug 1, 2025
      If your Lenze AC Tech Control Unit drive stops for no obvious reason, it could be due to one of the PROFIBUS-DP monitoring messages timing out, with its time-out reaction set to STOP. To resolve this, identify the time-out message (P423...P429) and modify the appropriate time-out time or reaction to the time-out settings.
  • J
    Justin WatkinsAug 7, 2025
    What to do if PROFIBUS-DP write commands are ignored by Lenze AC Tech Control Unit?
    • R
      Rebecca SmithAug 7, 2025
      If PROFIBUS-DP write commands are ignored or return exceptions on your Lenze AC Tech Control Unit, the “Network enabled” terminal is either open or not configured. To fix this, configure one of the input terminals (P121, P122 or P123) to the "Network Enabled" function (selection 9) and close the corresponding contact.
  • J
    Joshua LawsonAug 13, 2025
    Why Lenze AC Tech Control Unit module does not enter Data Exchange State?
    • T
      timothymcdowellAug 13, 2025
      If the Lenze AC Tech Control Unit module does not enter the Data Exchange State and P419 displays 2 or 3, this could be due to a data size configuration mismatch between the Master and the Drive. Check the configuration sizes for Dout and Din Data, referring to parameters P415 and P416.
  • Y
    yschmittAug 18, 2025
    How to make Lenze AC Tech Control Unit drive change direction to REVERSE?
    • C
      christopher84Aug 18, 2025
      If the Lenze AC Tech Control Unit drive does not change direction to REVERSE, it is possible that parameter P112 is set to 0 (Forward Only). To enable both Forward & Reverse directions, set drive parameter P112 to 1.

Summary

Safety Information

Warnings, Cautions and Notes

General safety advice, including warnings, cautions, and notes for operation.

Installation and Electrical Safety

Safety precautions for physical installation, electrical connection, and regulatory compliance.

Operational Safety

Safety considerations for operating the drive controller and system.

Installation Guide

Mechanical Installation

Steps for physically mounting the PROFIBUS-DP module onto the drive.

PROFIBUS-DP Terminal Block

Description of the PROFIBUS-DP connector terminals and their functions.

Electrical Installation and Network Setup

Guidance on cable types, network limitations, connections, and termination.

Commissioning the PROFIBUS-DP Module

SMV Module Configuration Steps

Connecting, setting protocol, node address, baud rate, and data mapping.

Cyclic Data Access

Cyclic Data Details and Status

Acyclic Parameter Access

4 WPA Format and Parameter Access

Details on 4WPA format, function codes, and parameter access.

Diagnostics and Troubleshooting

Troubleshooting Common Issues

Common issues, causes, and remedies for module operation.

Parameter Quick Reference

Lenze AC Tech ESVZAP0 Specifications

General IconGeneral
Output Frequency0 - 400 Hz
Input Frequency50/60 Hz
Weight1.5 kg
Control MethodV/f Control
Protection FeaturesOvervoltage, Undervoltage, Short Circuit
Operating Temperature-10°C to +40°C
Storage Temperature-20°C to +60°C
Humidity5 - 95% non-condensing