SF01U 35
P04 STOP METHOD
01 COAST TO STOP: When a STOP command is given, the drive shuts off the output to
the motor, allowing it to coast freely to a stop.
02 COAST WITH DC BRAKE: When a stop command is given, the drive will activate DC
braking (after a delay of up to 2 seconds, depending on frequency) to help decelerate the
load. Refer to Parameters: 21 - DC BRAKE TIME, and 22 - DC BRAKE VOLTAGE.
03 RAMP TO STOP: When a stop command is given, the drive will decelerate the motor to
a stop at the rate determined by Parameter 20 - DECELERATION TIME.
04 RAMP WITH DC BRAKE: When a stop command is given, the drive will decelerate the
motor down to 0.2 Hz (at the rate set by Parameter 20 - DECELERATION TIME) and
then activate DC braking according to the settings of Parameters 21 - DC BRAKE TIME
and 22 - DC BRAKE VOLTAGE. This is used to bring the load to a final stop, as the
motor may still be turning slightly after the drive stops.
P05 STANDARD SPEED SOURCE
This selects the speed reference source when the drive is in STANDARD speed mode. The
following speed references can be selected:
01 KEYPAD: Use the and buttons to scroll to the desired speed.
02 PRESET SPEED #1: The drive will operate at the frequency set into Parameter 31.
03 0 - 10 VDC: The drive will respond to a 0-10 VDC signal wired to TB-2 and TB-5.
04 4 - 20 mA: The drive will respond to a 4-20 mA signal wired to TB-2 and TB-25.
P06 TB-14 OPEN COLLECTOR OUTPUT
This selects the status indication for the open-collector output at TB-14. The terms “open” and
“close” refer to the state of the internal transistor that activates the circuit. When the transistor
is “closed”, TB-14 is at the same potential as TB-2, allowing current to flow.
01 NONE: Disables the open-collector output.
02 RUN: Closes upon a START command. Opens if the drive is in a STOP state, the drive
faults, or input power is removed. DC braking is considered a STOP state.
03 FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power is
removed.
04 INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition.
05 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts
are unsuccessful, or if input power is removed.
06 AT SET SPEED: Closes if the drive is within + 0.5 Hz of the speed setpoint.
07 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds the PRESET SPEED
#3 setting. Opens if the output frequency is equal to or less than PRESET SPEED #3
(Parameter 33).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze AC Tech SF210 and is the answer not in the manual?

Lenze AC Tech SF210 Specifications

General IconGeneral
BrandLenze AC Tech
ModelSF210
CategoryController
LanguageEnglish

Related product manuals