Code Name Parameter
(Factory settings are printed in bold)
Acceptance see
page
Your
settings
C119 Preselection:
Monitoring
-0- Digital input TRIP set
-1- PTC input
-15- Inverter overload (I t monitoring)
-16- Motor overload (I
2
t monitoring)
SH + PRG 97,
98
C120 Function for
C119
For C119 = -0-. -1-
-0- Monitoring not active
-1- Monitoring active, sets TRIP
-2- Monitoring active, sets warning
For C119 = -15-
-0- Rated power for temperature range up
to 50°C
-1- Increased power for temperature
range up to 45°C
-2- Maximum power for temperature
range up to 40°C
For C119 = -16-
-0- Monitoring not active
-1- Monitoring active, sets TRIP
SH + PRG 97,
98
C125* Baud rate
(only for
LECOM)
-0- 9600 baud
-1- 4800 baud
-2- 2400 baud
-3- 1200 baud
SH + PRG 111
C130 Enable
additional pair
of ramp times
(main set-
value)
-0- Acceleration and deceleration time
(C012 and C013) active/activate
-1- Additional pair of ramp times 1
active/activate
-2- Additional pair of ramp times 2
active/activate
... ...
-15- Additional pair of ramp times 15
active/activate
SH + PRG 81
C131 Ramp gener.
stop (main set-
value)
-0- Ramp generator enabled
-1- Ramp generator stopped
SH + PRG 84
C132 Ramp
generator input
= 0 (main set-
value)
-0- Ramp generator input enabled
-1- Ramp generator input = 0/
set to zero
SH + PRG 84
C134 Ramp gener.
characteristic
(main set-
value)
-0- linear characteristic
-1- S-shaped characteristic
[SH + PRG] 93
C142* Flying restart
circuit
-0- No flying restart
-1- Flying restart in the selected direction of
rotation
-2- Flying restart in both directions of rotation
[SH + PRG] 95
C143* Threshold for
automatic
chopping
frequency
reduction to 2
kHz
0.0Hz 0.0 to 10.0Hz
0.0Hz = automatic chopping frequency
reduction switched off
(in steps of 0.1Hz)
ON-LINE 92
C160* Display of
process step
-0- Process step not active /finished
-x- Process step x is active
94
C161-
C168
Stored fault
indications
Display of stored fault indications, only readable via
LECOM
111,
117
C172* Set-value input -0- Set-value 1 (C046) and feedback of PI
controller (C051) as relative value
-1- Set-value 1 (C046) and feedback of
PI controller (C051) as absolute value
[SH + PRG] 64
C176* Function
terminals 21,
22
-0- Terminal 21: Remove quick stop
Terminal 22: Remove quick stop,
invert main set-value
-1- Terminal 21: Invert main set-value
Terminal 22: Remove quick stop
[SH + PRG] 59