Parameter setting
Parameter setting using the keypad
9
l
EDKVF9333 EN 1.0
For terminal control
You can change to other parameter sets via e.g. the digital inputs X5/E1...X5/E5.
After mains connection, the contr oller reads parameter set 1 first. Then, the terminals are evaluated
and the desired parameter set is loaded. A LOW-HIGH edge at input DCTRL-PAR-LOAD (Load
parameter set) is not necessary in this case:
One or two ditital inputs must be assigned to Select parameter set in every parameter set.
Determine the source(s) for Select parameter set under C0880. The signal names are:
DCTR L-PAR* 1 and DCTRL-PAR *2.
One digital input must be assigned to Load parameter set in every parameter set:
Determine the source for Load parameter set under C0881.The signal name is:
DCTR L-PAR-LOAD.
T hese inputs must have the same assignment in all parameter sets which you want to use.
T he controller reads the terminals assigned with Select parameter as a binary code. The
input DCT RL-PAR*1 is the first input, the input DCTRL-PAR*2 is the second input (e.g. E 1 =
first input, E 2 = second input).
The signal must be applied constantly at the terminals for at least 10 ms so that the
parameter set to be loaded is recognized correctly.
Terminal signals to select parameter sets:
1st input (DCTRL-PAR*1) 2nd input (DCTRL-PAR*2)
Parameter set 1 LOW LOW
Parameter set 2 HIGH LOW
Parameter set 3 LOW HIGH
Parameter set 4 HIGH HIGH
A LOW-HIGH edge at the input Load parameter set DCTR L-PAR-LOAD changes to the new
parameter set.
Procedure:
1. Trigger digital inputs, which are assigned to the function Select parameter set.
2. Inhibit contr oller with X5/28 = LOW.
3. Trigger LOW-HIGH edge at the input Load parameter set” .
4. When the loading is completed:
C0002 displays the number of the loaded parameter set.
RDY is illuminated.
5. E nable controller with X 5/28 = HIGH.