Parameter setting
Parameter setting using the keypad
8
l
EDKVF9333 EN 1.0
2.2.4 Load parameter set
(possible only when the controller is inhibited)
Warning!
When a new parameter set is loaded, the controller is reinitialised and acts as if it was
connected to the mains:
System configurations and terminal assignments may be changed. E nsur e, that your wiring
and drive configuration correspond to the settings of the parameter set.
Only use terminal X5/28 as a source for controller inhibit! Otherwise the drive may start
accidentally when changing to another parameter set.
Tip!
T he R DY message is not displayed while the parameter set is loaded since the controller cannot
be operated then.
Mains connection
T he controller automatically loads parameter set 1.
Via keypad
1. X5/28 = LOW
2. Select C0810/1 using
Y
or
B
select C0002.
3. Change to the parameter level using PR G .
4. Select C0810/1 using
Y
or
B
select the desired parameter set.
5. Press SHIF T + PRG .
OK” is displayed. When OK” is no longer displayed, the loading is completed.
6. E nable controller with X 5/28 = HIGH.