Networking
Networking with E82ZAFCC system bus function module (CAN)
10
Function library
10.19
10.19.1
L
10.19-2
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0354*
v
Selective system
bus address
0 {1} 513 • Only for the E82ZAFCC system bus
function module on the FIF interface.
• Individual addressing of system bus
process data objects
^
10.19-1
1 CAN-IN1 (sync) 129
Effective with sync control (C0360 = 1)
2 CAN-OUT1 (sync) 1
3 CAN-IN2 257
4 CAN-OUT2 258
5 CAN-IN1 (time) 385
Effective with event and time control
6 CAN-OUT1 (time) 386
(C0360 = 0)
C0355*
v
System bus
identifier
0 {1} 2047 • Only for the E82ZAFCC system bus
function module on the FIF interface.
• Only display
^
10.19-1
1 CAN-IN1
Identifier of CAN1 with sync control (C0360
2 CAN-OUT1
=1)
3 CAN-IN2
4 CAN-OUT2
5 CAN-IN1
Identifier of CAN1 with event or time
6 CAN-OUT1
control (C0360 = 0)
C0356*
v
System bus time
settings
Only for the E82ZAFCC system bus function
module on the FIF interface.
^
10.19-1
1 Boot up 3000
0 {1 msec} 65000
Required for CAN network without master
2 Cycle time
CAN-OUT2
0
0 = event-controlled process data transfer
> 0 = cyclic process data transfer
3 Cycle time
CAN-OUT1
0 0 and C0360 = 0: event-controlled process
data transfer
> 0 and C0360 = 1: cyclic process data
transf er
4 CAN delay 20 Waiting t ime until cyclic sending aft er
boot-up
C0357*
v
System bus
monitoring times
Only for the E82ZAFCC system bus function
module on the FIF interface.
^
10.19-1
1 CAN-IN1 (sync) 0
0
= monitoring not
{1 msec} 65000
active, if C0360 = 1
TRIP CE1 a t communication abort
2 CAN-IN2 0
active
TRIP CE2 a t communication abort
3 CAN-IN1 (time) 0 active, if C0360 = 0
TRIP CE3 a t communication abort
C0358*
Reset node 0
0 Without function
• Only for the E82ZAFCC system bus
^
-
1 System bus reset
unc
on mo
u
eon
e
n
er
ace.
• Syst em bus reset node set-up
.
-
C0359* System bus status
0 Operational
• Only for the E82ZAFCC system bus ^
v
1 Pre-operational
function module on the FIF interface.
10.19-1
2 Warning
• Only display
3 Bus off
C0360* Control of process
1
0 Event or time control
Only for the E82ZAFCC system bus function
v
data channel CAN1
1 Sync control
module on the FIF interface.